YOUR PARTNER IN MAINTENANCE Repair this product with RGB ELEKTRONIKA ORDER A DIAGNOSIS LINEAR ENCODERS SYSTEMS INDUSTRIAL COMPUTERS ENCODERS CONTROLS SERVO AMPLIFIERS MOTORS MACHINES OUR SERVICES POWER SUPPLIERS OPERATOR SERVO PANELS DRIVERS At our premises in Wrocław, we have a fully equipped servicing facility. Here we perform all the repair works and test each later sold unit.
Page 5
Axis Expansion Manual I/O Modules NCU Terminal Block DMP Compact Modules Maintenance and Service Abbreviations Valid for References Control Software Version SINUMERIK 810D SINUMERIK 810DE (export version) EC Declaration of SINUMERIK 810D powerline Conformity SINUMERIK 810DE powerline Index 11.2002 Edition...
Page 6
Trademarks SIMATICr, SIMATIC HMIr, SIMATIC NETr, SIROTECr, SINUMERIKr and SIMODRIVEr are registered trademarks of Siemens AG. Other product names used in this documentation may be trademarks which, if used by third parties, could infringe the rights of their owners. Further information is available on the Internet under: Other functions not described in this documentation might be executable in the control.
SINUMERIK documentation is split into three levels: reader General Documentation User Documentation Manufacturer/Service Documentation. For more detailed information on SINUMERIK 810D publications and other pu- blications covering all the SINUMERIK controls, please contact your local SIE- MENS office. You will also require the following References:...
Page 8
Caution This warning notice (without a warning triangle) indicates that some material damage may occur if the relevant safety precautions are not taken. E Siemens AG, 2002. All rights reserved SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 9
Warning Repairs to devices that have been supplied by our company must only be carried out by SIEMENS Customer Service or by repair centers author- ized by SIEMENS. When replacing parts or components, only use those parts that are included in the spare parts list.
Page 10
The simplest way of doing this is to touch an electrically conducting earthed object (e.g. a bare metal part of a switchboard or a plug socket protective conductor). E Siemens AG, 2002. All rights reserved viii SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 11
SIEMENS. Contact persons Should any problems or questions arise while you are using this manual, please contact the Siemens office concerned using the form provided at the end of this manual. E Siemens AG, 2002. All rights reserved...
Page 12
Planning Guide SINUMERIK 810D 12.95 Preface Notes E Siemens AG, 2002. All rights reserved SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Note The SINUMERIK 810D powerline and SINUMERIK 810DE powerline are supplied with SW 6. Earlier system software versions of the SINUMERIK 810D cannot be used on SINUMERIK 810D powerline or SINUMERIK 810DE powerline. E Siemens AG, 2002. All rights reserved 1-13 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
6FC5 412- -0FA10- -0AA0 For installing in a SIMODRIVE 611 power module (1-axis or 2-axis), plug- -in unit References: /PJ/, SIMODRIVE 611 Planning Guide E Siemens AG, 2002. All rights reserved 1-14 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 17
Single I/O module 6FC5 411-0AA00-0AA0 PLC I/O module with 64 inputs and 32 short-circuit-proof outputs (EFP) NCU terminal 6FC5 211-0AA00-0AA0 High-speed digital and analog NC I/Os on the SINUMERIK 810D drive bus block Handheld unit 6FX2 007-1AC.. Handheld unit with...
1FNx, 1FEx, 1FKx *) One measuring output can be replaced by a 3rd handwheel Fig. 1-1 The SINUMERIK 810D system showing example of CCU3 E Siemens AG, 2002. All rights reserved 1-16 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 19
MPI bus cable PG740 programming device MPI cable Fig. 1-2 SINUMERIK 810D connection configuration for the MPI bus, HHU, HPU and cable distributor E Siemens AG, 2002. All rights reserved 1-17 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Single I/O module Terminator Do not exceed maximum configuration !! Fig. 1-3 SINUMERIK 810D connection configuration for PLC I/Os and NCU terminal block E Siemens AG, 2002. All rights reserved 1-18 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
03.02 1 System Overview 12.95 1.2 System configuration Interconnecting The following interconnecting cables are used for the SINUMERIK 810D cables Table 1-3 Interconnecting cables for the SINUMERIK 810D Order No. Designation 6FX2 002-4EA0V-1VV0 MPI bus cable from operator panel front to MCP and CCU...
Page 22
Axis expansion plug--in units are always used when no more than six measu- plug in unit ring channels are required for the SINUMERIK 810D. The unit is plugged into a SIMODRIVE 611 power module. Axis expansion plug in units are designed for axis and 2 axis power modules.
Page 23
11.02 1 System Overview 12.95 1.2 System configuration Table 1-4 Possible combinations for 1- -6 drives with the SINUMERIK 810D Number of Internal drives Drives via axis drives 1 x 18/36A (FDD) expansion *or 24/32A (MSD) 2x9/18 / 2 x 6/12A...
Page 24
The length of the cable set for axis expansion with the 611D closed-loop control module is: 62mm for the drive bus and 150mm for the device bus. E Siemens AG, 2002. All rights reserved 1-22 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
1.3 Labeling and adhesive labels Labeling and adhesive labels If you contact your local Siemens office for technical information or because servicing is necessary, please provide all data given on the rating plate. The components and modules are provided with one of the following labels:...
Page 26
The simplest way of doing this is to touch an electrically conducting earthed object (e.g. a bare metal part of a switchboard or a plug socket protective conductor). E Siemens AG, 2002. All rights reserved 1-24 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Reference: /EMV/, EMC Installation Guideline information Assistance and The installation conditions must be complied with for the complete system. Please contact your local Siemens office or representative for assistance and advice advice. E Siemens AG, 2002. All rights reserved 2-25...
Note Radio interference suppression must be considered by the user for the complete installation. Particular attention should be paid to cables. Please contact your local Siemens office or representative for assistance and advice. Noise immunity Relevant standards: EN 50178, EN 61000-3-2 and -3-3,...
If necessary, these interfaces can be isolated safely using a supplementary adapter (insulation voltage 230VAC). These adapters are not included in the Siemens scope of delivery. You can buy these parts from your local dealer who will help you to make the proper choice.
Page 32
230 VAC are provided for these interfaces. 11. 5VDC power supply with basic insulation, fed from a 24VDC supply. E Siemens AG, 2002. All rights reserved 2-30 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Signal cables must not be routed close to strong external magnetic fields (e.g. motors and transformers). Pulse-loaded heavy current/high voltage cables must always be laid completely separate from all other cables. E Siemens AG, 2002. All rights reserved 2-32 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 35
For further information on interference suppression measures and the connection of shielded cables refer to References: /EMC/ SINUMERIK, SIROTEC, SIMODRIVE EMC Installation Guideline E Siemens AG, 2002. All rights reserved 2-33 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Applicable standards: DIN EN 60086(-4) Warning Improper handling of backup batteries involves the risk of ignition, explosion and burning. E Siemens AG, 2002. All rights reserved 2-34 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
When operated at an 86kPa to 108kPa altitude 1500m above mean sea level. For greater altitudes, the upper limit temperature must be reduced by 3.5C/500m. E Siemens AG, 2002. All rights reserved 2-35 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
6. The following cable lengths for MPI may not be exceeded for the standard case without repeater: MPI (187.5 kbaud): Max. cable length in total 10m. E Siemens AG, 2002. All rights reserved 2-39 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 42
2 Installation Conditions 11.02 12.95 2.4 MPI network Notes E Siemens AG, 2002. All rights reserved 2-40 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Delivery condition: Internal cooling. Modification: Use a screwdriver (Torx for M6) to unscrew the mounting bracket and fit the four grounding springs (see installation instructions) E Siemens AG, 2002. All rights reserved 3-41 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
12.95 3.2 Installing the SINUMERIK 810D Installing the SINUMERIK 810D Preparation For assembling the SINUMERIK 810D control, you need the following tools: Screwdriver for slotted screws size 0 and 1 Screwdriver for M4 and M5 Torx screws. Position in the...
Page 45
The slotted screws (1) must be tightened (see Fig. 3-3) to ensure compliance with EMC requirements and to guarantee the necessary vibration resistance. E Siemens AG, 2002. All rights reserved 3-43 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 46
Fig. 3-3 Assembling the SINUMERIK 810D Installation notes When mounting the SINUMERIK 810D, please observe the following points: 1. Ventilation gap above and below approx. 100mm 2. The shields of the motor leads must be connected after the shield plate has been installed, see Subsection 2.1.4.
Page 47
2-axis CCU box, see the shield plate installation diagram). The shield plate is included in the box. The tube clip for shield connection is included in the scope of supply for the preassembled SIEMENS motor connecting lead.
Page 48
Important! The shield Phone: Phone: ++49-(0)6181-403-0 attachment is no pull- - relief Fax: ++49-(0)6181-403-210 Fig. 3-5 Dimension drawing of the 2 axis CCU box E Siemens AG, 2002. All rights reserved 3-46 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Loosen screws M6 and remove angle Put on ground spring (packed in flat bag) Fig. 3-7 2-axis CCU box: Modification for external cooling E Siemens AG, 2002. All rights reserved 3-47 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 50
*in the case of the SIEMENS motor lead, included in the scope of supply Fig. 3-8 Connecting the motor and encoder leads (3-axis CCU box) E Siemens AG, 2002. All rights reserved 3-48 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
197-0AA00 Planning Guide (setting options, technical data, recommended circuits). Warning The equipment is still under hazardous power for approx. 5 minutes after all power has been disconnected. E Siemens AG, 2002. All rights reserved 3-49 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 52
3 Design and Installation of the 810D 12.95 12.95 3.3 Mains supply (MS) Notes E Siemens AG, 2002. All rights reserved 3-50 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
SW 2.x and lower: The system software of the SINUMERIK 810D is stored on an internal flash EPROM and is included in the scope of supply (also valid for CCU3 Export SW 6). The PCMCIA card is only used when the software is upgraded. Also valid for CCU3 Export.
Page 54
The following are not available: for NCU 840D 5-axis transformation Safety Integrated Analog axis Hydraulic drives Independent drive stop/retract 3D clearance control. E Siemens AG, 2002. All rights reserved 4-52 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 55
Smooth running 0.2←m 1.5←m 0.1←m 0.2←m 0.1←m approx. 1.5←m Pulse multiplication 2048 2048 factor As from drive software version 6.4.2 for FDD single/axis E Siemens AG, 2002. All rights reserved 4-53 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Operator control elements for start--up, delete, reset Four test sockets for diagnostics Device bus interface. CCU3 The CCU3 module has an additional pulse interface. E Siemens AG, 2002. All rights reserved 4-54 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
X304- -X306 Device bus interface X151 Fig. 4-1 SINUMERIK 810D with CCU 1/2, position of the interfaces, operating and display elements E Siemens AG, 2002. All rights reserved 4-56 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Connection of S7-300 I/O devices and single I/O module Connector designation: X111 Connector type: 25-way sub-D socket connector Maximum cable length: Special features: Non-floating, no safe isolation E Siemens AG, 2002. All rights reserved 4-57 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 60
I/O device interface (cable distributor for handwheel and probe) Connector designation: X121 Connector type: 37-pin sub-D plug connector Maximum cable length: 25m for all functions Special features: Handwheels non-floating E Siemens AG, 2002. All rights reserved 4-58 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 61
Pin assignment on connector X122 X122 Name Type Name Type Unassigned P5EXT M24EXT P24EXT ORTSAS IRTSPG M5EXT Signal names Same as X102, as appropriate (Tab. 4-3) E Siemens AG, 2002. All rights reserved 4-59 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 62
Connector designation: X411-X416 Connector type: 25-way, sub-D plug connector The signals with a gray background are not required for a direct measuring system. E Siemens AG, 2002. All rights reserved 4-60 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 63
Remote/Sense mode. As a result, the length of the encoder cable is limited. ± 18m EQN 1325: ERN 1387: ± 25m External encoder with power consumption ± 300mA: ± 18m E Siemens AG, 2002. All rights reserved 4-61 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 64
The “startup disable” relay is switched with terminal 663. When the contact is opened, the actuation pulses are disabled and the motors are switched to torque-free mode. E Siemens AG, 2002. All rights reserved 4-62 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 65
7- -segment error messages DAC test sockets DAC 2 DAC 1 Ground DAC 3 Fig. 4-2 DAC test sockets on the CCU1/2 modules E Siemens AG, 2002. All rights reserved 4-63 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 66
(axes 4- -6) Drive bus interface X151 Fig. 4-3 SINUMERIK 810D with CCU 3, position of the interfaces, operating and display elements E Siemens AG, 2002. All rights reserved 4-64 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 67
PLC STOP status (right Lights up if a PLC error occurs row) Yellow PFO: PLC FORCE status Yellow RST: Lights up briefly on reset E Siemens AG, 2002. All rights reserved 4-65 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
By fastening them to the front panel of the CCU, the shield potential is conducted via the contact springs of the cable distributor. E Siemens AG, 2002. All rights reserved 4-66 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 70
Measuring pulse signal 0/1 MEPUC 0/1 Measuring pulse common (reference ground) 0/1 1) Total of max. 1A, i.e. max. 500mA for each handwheel E Siemens AG, 2002. All rights reserved 4-68 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Note the encoder signal frequency response. 0.5V A--A 0.5V B--B Uniqueness range R--R Fig. 4-7 Signal chart for incremental encoders at clockwise rotation E Siemens AG, 2002. All rights reserved 4-70 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 73
± ¦ Note the encoder signal frequency response. A- -A B- -B Fig. 4-8 Signal chart for incremental signals at clockwise rotation E Siemens AG, 2002. All rights reserved 4-71 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
4.3.3 Measuring channels, indirect and direct measuring systems Measuring The six measuring channels on the SINUMERIK 810D can be used both for channels on the indirect and for direct position sensing. A spare measuring channel can be used for a direct spindle measuring system, for example. To obtain additional measu-...
Page 75
CCU module loop control G = 0.006 degrees Motor Multiturn absolute: 4096 revolutions Fig. 4-9 Indirect position sensing with digital closed-loop control FDD E Siemens AG, 2002. All rights reserved 4-73 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 76
Voltage signals and Incremental EnDat absolute motor position Indirect position sensing with digital closed-loop control FDD Fig. 4-10 *) e.g. 1FK7 E Siemens AG, 2002. All rights reserved 4-74 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 77
CCU module oop control G = 0.006 degrees Motor *) Indirect position sensing with digital closed-loop control MSD Fig. 4-11 *) e.g. 1PH7 E Siemens AG, 2002. All rights reserved 4-75 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 78
Only encoders with voltage signals can be used with the SINUMERIK 810D. Direct position sensing M: Max. possible measuring steps...
4.4 Integrated power sections: 3-axis CCU box Integrated power sections: 3-axis CCU box Description With the SINUMERIK 810D, three integrated power sections are mounted in the 3-axis CCU box on a heatsink: Power section for 2x 6A/12A (FDD) Power section for 1x 18A/36A (FDD) or 24A/32A (MSD) Heatsink temperature sensor.
Page 80
At simultaneous continuous operation, power sections A2 and A3 must only (GZF) operate on average at 63% of their rated current. There is no simultaneity restriction for A1. E Siemens AG, 2002. All rights reserved 4-78 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
4.5 Integrated power sections: 2-axis CCU box Integrated power sections: 2-axis CCU box Description With the SINUMERIK 810D, two integrated power sections are mounted in the 2-axis CCU box on a heatsink: Power section for 9A/18A (FDD) Heatsink temperature sensor.
A slot is available on the CCU for standard PC cards supporting all Type II flash cards up to 8MB memory capacity. Recommendation: use Siemens PC cards. E Siemens AG, 2002. All rights reserved 4-80 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Axis expansion plug-in unit Application The axis expansion plug-in unit is mounted in a SIMODRIVE 611 power module and then connected to the SINUMERIK 810D at axis expansion terminal X304--X306. The plug-in unit is designed for use in 1-axis and 2-axis power modules.
X301. If you are using a 2-axis power section, connector X301 is assigned to the first axis and connector X302 to the second axis. E Siemens AG, 2002. All rights reserved 5-84 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 87
CCU, push the excess length of cable into the space provided under the metal cover of the axis expansion plug-in unit. E Siemens AG, 2002. All rights reserved 5-85 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Installation The SIMODRIVE 611D module is mounted as the first module to the right of the SINUMERIK 810D. When connecting the DC link busbars, all screws must be tightened (note the torque). Connection You need a special cable set to connect the SIMODRIVE 611D closed loop control module.
Page 89
810D. Drive bus cable Device bus cable Fig. 5-5 Cable set for axis expansion with the SIMODRIVE 611D module E Siemens AG, 2002. All rights reserved 5-87 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 90
04.00 5 Axis Expansion 12.95 5.2 Axis expansion with the SIMODRIVE 611D closed-loop control module Notes E Siemens AG, 2002. All rights reserved 5-88 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 91
The single I/O module has 64 inputs and 32 short-circuit-proof outputs (isolated). Each output has a load rating of 0.5A. The simultaneity factor is 75%. Up to three single I/O modules can be connected to the SINUMERIK 810D. Combinations with SIMATIC S7-300 phases are permissible.
VDE 0100 and VDE 0160 must always be complied with. E Siemens AG, 2002. All rights reserved 6-90 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 93
Resistance to vibration to SN 29010 Class 12 Temperature range - -40 C to +70 C Storage: 0 C to + 55 C Operation: E Siemens AG, 2002. All rights reserved 6-91 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 94
P24 power Signal names P24 power 24V external load power supply M24 power Ground of external load power supply Signal type Voltage Input E Siemens AG, 2002. All rights reserved 6-92 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 95
OUT26 OUT27 OUT30 OUT31 OUT32 OUT33 OUT34 OUT35 OUT36 OUT37 Signal names OUTiξjζ Output j of output byte i Signal type Output E Siemens AG, 2002. All rights reserved 6-93 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 97
The address space is automatically assigned during start-up. Parameterization is not necessary. In AS-PARAM, the 810D I/Os are treated like a corresponding arrangement of S7-300 modules. E Siemens AG, 2002. All rights reserved 6-95 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 98
AS314 (CCU1) AS315 (CCU2/3) Single I/O module Single I/O module Single I/O module Fig. 6-3 SINUMERIK 810D with three peripheral lines (full configuration) E Siemens AG, 2002. All rights reserved 6-96 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
I/O devices). The round cables are also used to connect the individual terminal blocks. Important Ensure that the overall length of the cable connections does not exceed 10m. E Siemens AG, 2002. All rights reserved 7-97 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
30 cm, if possible. DMP compact A maximum of eight DMP compact modules can be connected for each NCU modules terminal block. E Siemens AG, 2002. All rights reserved 7-98 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 101
Ambient temperature Temperature sensor Status message to NC, Screen display NCU sign-of-life Cyclic message Disabling of the NC outputs, LED (red) on E Siemens AG, 2002. All rights reserved 7-99 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 102
Max. length of drive bus is 10m X11- -X18 Module connector Connector designation: X11 ... X18 (slots 1 ... 8) Connector type: 30-way ELCO Microleaf pin connector E Siemens AG, 2002. All rights reserved 7-100 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 103
Temperature variation within 1 minute max. 0.2K Permissible change in relative air humidity EN 60721-3-3, class 3K5 Within 1 minute max. of 0.1% E Siemens AG, 2002. All rights reserved 7-101 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 104
7 NCU Terminal Block 12.95 Notes E Siemens AG, 2002. All rights reserved 7-102 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
The 24V connection terminal P (24V) is not used. Display elements 16 LEDs for status display indicating the logical states of the inputs. LEDs light up: Input ON. E Siemens AG, 2002. All rights reserved 8-103 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 106
= type 1msec Cable length max. 30m Weight approx. 125g Degree of protection according to DIN 40050 IP20 Humidity rating according to DIN 40040 E Siemens AG, 2002. All rights reserved 8-104 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
20.4V to 28.8V - Ripple 3.6Vpp Signal level of outputs (typical value) - For “0” signal Open - For “1” signal - -250mV LOAD E Siemens AG, 2002. All rights reserved 8-105 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 108
All 16 outputs may be loaded simultaneously, e.g. with 0.25A. Important Switching surges must be neutralized by external free-wheeling diodes when using inductive loads. E Siemens AG, 2002. All rights reserved 8-106 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Eight LEDs as status display for the logic output states. As from product version B the LEDs will go out if the load voltage fails. LEDs light up: Output ON. E Siemens AG, 2002. All rights reserved 8-107 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 110
All 8 outputs may be loaded simultaneously, e.g. with 1A. Important Switching surges must be neutralized by external free-wheeling diodes when using inductive loads. E Siemens AG, 2002. All rights reserved 8-108 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Setting of measuring range 1--2 closed: + 10V 1--3 closed: + 500mV Setting of mains frequency closed: for 50Hz systems open: for 60Hz systems. E Siemens AG, 2002. All rights reserved 8-109 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 112
Operating error limits (0_C to 60_C) Cable length (shielded) max. Weight approx. 150g Degree of protection according to DIN 40050 IP20 Humidity rating according to DIN 40040 E Siemens AG, 2002. All rights reserved 8-110 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 113
OR= Overflow bit, input voltage exceeds 20V or 1V (double the input range) PF = Failure of power supply to analog part. E Siemens AG, 2002. All rights reserved 8-111 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
The terminals are of the plug-in type and can be mechanically coded by the user. Display elements One LED as status display for power supply. LED lights up: internal power supply OK. E Siemens AG, 2002. All rights reserved 8-112 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 115
The resolution is 4.88mV for one bit. The duration of a converter cycle (from initiating the conversion until the moment the result can be read) is max. 75μsecs. E Siemens AG, 2002. All rights reserved 8-113 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 116
0.005V Digital value - -0.005V - -9.995V - -10V 0 = Always 0 PF = Failure of power supply to analog part E Siemens AG, 2002. All rights reserved 8-114 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
The terminals are of the plug-in type and can be mechanically coded by the user. Display elements One LED as status display for power supply. LED lights up: internal power supply OK. E Siemens AG, 2002. All rights reserved 8-115 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 118
QB m+1 output voltage voltage Signifi- cance cance VZ 2 VZ 2 always always +9.9988V +1.22mV Digital value - -1.22mV - -10V E Siemens AG, 2002. All rights reserved 8-116 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Warning After all voltages have been switched off, a dangerous voltage remains present for five minutes at all modules. See operating instructions. E Siemens AG, 2002. All rights reserved 9-117 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
PCU 50/70. The back--up voltage is monitored by the control and a monito- ring signal is output. When a monitoring signal has been triggered, the battery must be replaced within six weeks. The battery of the SINUMERIK 810D can be replaced after disconnecting the control and removing the CCU module without any loss of data, as the data is backed--up for a period of approx.
Page 121
6. Connect the new battery (check polarity) and push it back into the bracket. 7. Re-insert the CCU module and tighten the screws. 8. Insert all the connectors correctly. E Siemens AG, 2002. All rights reserved 9-119 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 122
9 Maintenance and Service 12.95 9.2 Battery replacement (6FC5 247-0AA18-0AA0, GWE-570 665 000 101) Notes E Siemens AG, 2002. All rights reserved 9-120 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
The meaning of HMI is identical with MMC. Main Spindle Drive Handheld Terminal Interface Module (SIMATIC S7-300) IM Address Interface Module Address Industry Standard Architecture E Siemens AG, 2002. All rights reserved A-121 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 124
Power Supply (SIMATIC S7-300) Personal Computer Unit Signal Module SIMATIC S7-300, e.g. I/O module Software Unregulated Power Supply Video Graphics Adapter Feed Spindle Drive E Siemens AG, 2002. All rights reserved A-122 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Electronic Documentation /CD1/ The SINUMERIK system (Edition 11.02) DOC ON CD (containing all SINUMERIK 840D/840Di/810D/802 and SIMODRIVE documentation) Order no.: 6FC5 298-6CA00-0BG3 E Siemens AG, 2002. All rights reserved B-123 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Measuring Cycles User’s Guide (Edition 11.02) Order no.: 6FC5 298-6AA70-0BP2 /CAD/ SINUMERIK 840D/840Di/810D Operator’s Guide CAD-Reader (Edition 03.02) Order no.: (part of online help) E Siemens AG, 2002. All rights reserved B-124 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 127
Order no.: 6FX2 060 4AA00-4XB0 (Ger., Eng., Fr.) Order from: Fürth plant /SYI/ SINUMERIK 840Di System Overview (Edition 02.01) Order no.: 6FC5 298-6AE40-0BP0 E Siemens AG, 2002. All rights reserved B-125 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 128
(the books contained therein are listed below) Order no.: 6FC5 297-6AC20-0BP2 Various interface signals Axis monitoring protection zones Continuous-path mode, exact stop and look ahead Acceleration Diagnostic aids E Siemens AG, 2002. All rights reserved B-126 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 129
Contour tunnel monitoring Coupled axes and ESR Constant tool speed for centerless grinding Tangential control Installation and activation of compile cycles Clearance control E Siemens AG, 2002. All rights reserved B-127 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 130
Order no.: 6FC5 297-5AE50-0BP2 /FBDT/ SINUMERIK 840D/840Di/810D IT-Solutions SinDNC NC Data transmission via network (Edition 09.02) Description of Functions Order no.: 6FC5 297-5AE70-0BP0 E Siemens AG, 2002. All rights reserved B-128 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 131
Description of Functions SINUMERIK Safety Integrated (Edition 09.02) Order no.: 6FC5 297-6AB80-0BP1 /FBSP/ SINUMERIK 840D/810D Description of Functions ShopMill (Edition 11.02) Order no.: 6FC5 297-6AD80-0BP1 E Siemens AG, 2002. All rights reserved B-129 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 132
SINUMERIK 840D/840Di/810D Start-up tool SINUMERIK SinuCOM NC (Edition 02.02) System description Order no.: (supplied with the online help for the start-up tool) E Siemens AG, 2002. All rights reserved B-130 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 133
Planning Guide ECO motor spindles for main spindle drives Order no.: 6SN1 197-0AD04-0BP0 /POS1/ SIMODRIVE POSMO A (Edition 08.02) Decentralized Positioning Motor on PROFIBUS DP, User’s Guide Order no.: 6SN2197-0AA00-0BP3 E Siemens AG, 2002. All rights reserved B-131 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 134
Order together with the configuring package /SP/ SIMODRIVE 611-A/611-D, SimoPro 3.1 Program for Configuring Machine Tool Drives Order no.: 6SC6 111-6PC00-0BAj Order from: Fürth plant E Siemens AG, 2002. All rights reserved B-132 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 135
Order no.: 6FC5 297-6AE20-0BP2 Updates/options Supplementing the user interface Online Help Installation & Startup HMI Embedded Installation & Startup HMI Advanced Creating foreign language texts E Siemens AG, 2002. All rights reserved B-133 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 136
11.02 B References 12.95 Notes E Siemens AG, 2002. All rights reserved B-134 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
EC Declaration of Conformity E Siemens AG, 2002. All rights reserved C-135 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 138
Throttle I/O devs. Supply terminal All the components that according to the ordering information are approved for the system network of SINUMERIK 810D comply with directive 89/336/EC within the network. For conformity to the standards, see Appendix C. Note The sketch of the system configuration shows only the basic measures for conformance with directive 89/336/EC for a typical system configuration.
Page 139
IEC 61000-4-2 + A1 IEC 61000-4-11 VDE 0847 Part 4-3 10): VDE 0160 Part 100 IEC 61000-4-3 + A1 IEC 61800-3 ___________________________________ except SINUMERIK 810D E Siemens AG, 2002. All rights reserved C-137 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 140
09.01 12.95 Notes E Siemens AG, 2002. All rights reserved C-138 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 144
11.02 12.95 Notes E Siemens AG, 2002. All rights reserved Index-142 SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition...
Page 145
Suggestions SIEMENS AG Corrections A&D MC BMS for Publication/Manual: P.O. Box 3180 SINUMERIK 810D D-91050 Erlangen/Germany hardware Configuration (Phone +49-(0)-180-5050-222 [Hotline] Fax +49-(0)-9131-98-2176 [Documentation] Manufacturer/Service Documentation E--mail: motioncontrol.docu@erlf.siemens.de) Manual Sender Order No. 6FC5 297-6AD10-0AP1 Name Edition: 11.02 Company address/department Should you come across any misprints...