8.3.3
GOT Standard Ethernet Setting
The GOT can be connected to a different network by using the following interface.
• Standard Ethernet interface:
Set the [GOT IP Address] and [Subnet Mask] in the GOT built-in Ethernet interface.
• Extension Ethernet interface:
Set the [GOT Extension IP Address] and [Extension Subnet Mask] in the Ethernet interface for the Ethernet
communication module.
BootOS Version Z or higher is required to use the extension Ethernet Interface.
For details on writing the BootOS, refer to the following manual.
GT Designer3 (GOT2000) Screen Design Manual
The standard Ethernet interface and extension Ethernet interface use the same [Default Gateway].
Item
The GOT standard Ethernet settings
are applied on the GOT unit.
GOT IP Address
Select from GOT Setting List
Subnet Mask
Default Gateway
Peripheral S/W Communication Port
No.
Transparent
Port No.
The GOT extension Ethernet
settings are applied on the GOT
unit.
Enabling the extension Ethernet
GOT Extension IP Address
Extension Subnet Mask
Description
The standard Ethernet settings are applied on GOT.
Set the IP address of the Standard Ethernet interface.
(Default: 192.168.3.18)
Select the set GOT in the [GOT Setting List] dialog.
GT Designer3(GOT2000) Help
Set the subnet mask for the sub network. (Only for connection via router) If
the sub network is not used, the default value is set.
(Default: 255.255.255.0)
Set the router address of the default gateway where the GOT is connected.
(Only for connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for the communication with the peripheral S/W. (Default:
5015)
Set the GOT port No. for the transparent function.
(Default: 5014)
The extension Ethernet settings are applied on GOT.
Enable the extension Ethernet settings.
An error message will appear if all of the [Extension I/F Setting] in the [I/F
communication setting] dialog are used.
Always set on of the [Extension I/F Setting] to [Not used].
1.1.2 I/F communication setting
Set the IP address of the Extension Ethernet.
(Default: 192.168.5.22)
Set the subnet mask for the sub network. (Only for connection via router)
If the sub network is not used, the default value is set. (Default:
255.255.255.0)
Range
-
0.0.0.0 to 255.255.255.255
-
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
1024 to 65534
(Except for 5011 to 5013,
49153 to 49170)
1024 to 65534
(Except for 5011 to 5013,
49153 to 49170)
-
-
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255