ABB i-bus KNX Product Manual page 38

Knx/enocean gateway
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®

i-bus
KNX
TOPIC
NAME
Status_ Current Position
Status_ Service On/Off
Status_ Energy/Input Enabled
Status_ Energy Storage. Changed
Status_ Batery Capacity
Status_ Cover State
Status_ Temperature Sensor Failure
Kieback
Status_ Window Contact
&Peter
Battery
Status_ Actuator obstructed
Powered
/
Status_ Temperature
Thermokon
Battery
Control_ Poisition Setpoint
Powered
Control _ Temperature Setpoint
Control _ Temperature RC
Control _ Run Init Sequence
Control _ Lift Set
Control _ Valve Open
Control _ Valve Close
Control _ Reduction of Energy Consumption
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
EG/A 32.2.1
DATAPOINT TYPE
LENGTH
DPT_NAME
1 byte
DPT_Scaling
1 bit
DPT_Switch
1 bit
DPT_Enable
1 bit
DPT_Bool
1 bit
DPT_Alarm
1 bit
DPT_OpenClose
1 bit
DPT_Bool
1 bit
DPT_Window_Door
1 bit
DPT_Bool
2 bytes
DPT_Value_Temp
1 byte
DPT_Scaling
2 bytes
DPT_Value_Temp
2 bytes
DPT_Value_Temp
1 bit
DPT_Bool
1 bit
DPT_Bool
1 bit
DPT_Bool
1 bit
DPT_Bool
1 bit
DPT_Bool
FLAGS
DPT_ID R W T U
5.001
R
T
%
0 – Off; 1 - On
1.001
R
T
0 – Disable; 1 – Enable
1.003
R
T
0 – False; 1 - True
1.002
R
T
0 – No alarm; 1 - Alarm
1.005
R
T
0 – Open; 1 – Close
1.009
R
T
0 – False; 1 - True
1.002
R
T
1.019
R
T
0 - Closed; 1 - Open
0 – False; 1 - True
1.002
R
T
9.001
R
T
ºC
5.001
R
T
%
9.001
R
T
ºC
9.001
R
T
ºC
0 – False; 1 - True
1.002
R
T
0 – False; 1 - True
1.002
R
T
0 – False; 1 - True
1.002
R
T
0 – False; 1 - True
1.002
R
T
0 – False; 1 - True
1.002
R
T
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com
User's manual r1.5 eng
FUNCTION
37 / 47