Input Power Connection; Motor Connection - ABB ACS150 User Manual

Table of Contents

Advertisement

114

Input power connection

Voltage (U
)
1
Short-circuit capacity
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1

Motor connection

Voltage (U
)
2
Short-circuit protection
(IEC 61800-5-1, UL 508C)
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length
Technical data
200/208/220/230/240 VAC 1-phase for 200 VAC drives
200/208/220/230/240 VAC 3-phase for 200 VAC drives
380/400/415/440/460/480 VAC 3-phase for 400 VAC drives
±10% variation from converter nominal voltage is allowed as default.
Maximum allowed prospective short-circuit current at the input power connection as
defined in IEC 60439-1 is 100 kA. The drive is suitable for use in a circuit capable of
delivering not more than 100 kA rms symmetrical amperes at the drive maximum rated
voltage.
50/60 Hz ± 5%, maximum rate of change 17%/s
Max. ±3% of nominal phase to phase input voltage
0.98 (at nominal load)
0 to U
, 3-phase symmetrical, U
1
The motor output is short-circuit proof by IEC 61800-5-1 and UL 508C.
Scalar control: 0...500 Hz
0.01 Hz
See section
Ratings
on page 109.
1.5 · P
N
10...500 Hz
4, 8 or 12 kHz
R0: 30 m (100 ft), R1...R2: 50 m (165 ft)
With output chokes the motor cable length may be extended to 60 m (195 ft) for R0 and
100 m (330 ft) for R1...R2.
To comply with the European EMC Directive, use the cable lengths specified in the table
below for 4 kHz switching frequency. The lengths are given for using the drive with the
internal EMC filter or an optional external EMC filter.
4 kHz switching frequency
Second environment
1)
(category C3
)
First environment
1)
(category C2
)
1)
See the new terms in section
at the field weakening point
max
Internal EMC filter
30 m (100 ft)
-
Compliance with the IEC/EN 61800-3 (2004)
Optional external EMC filter
To be added
To be added
on page 119.