Freq Input - ABB ACS150 User Manual

Table of Contents

Advertisement

Index Name/Selection
1606
LOCAL LOCK
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
7 = ON
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
1607
PARAM SAVE
0 = DONE
1 = SAVE
1610
DISPLAY ALARMS
0 = NO
1 = YES
1611
PARAMETER VIEW
0 = ABB STANDARD
1 = OEM VIEW

18 FREQ INPUT

1801
FREQ INPUT MIN
0...16000 Hz
1802
FREQ INPUT MAX
0...16000 Hz
Description
Disables entering local control mode or selects the source for the local
control mode lock signal. When local lock is active, entering the local control
mode is disabled (LOC/REM key of the panel).
Local control is allowed.
Local control mode lock signal through digital input DI1. Rising edge of digital
input DI1: Local control disabled. Falling edge of digital input DI1: Local
control allowed.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Local control is disabled.
Local lock through inverted digital input DI1. Rising edge of inverted digital
input DI1: Local control allowed. Falling edge of inverted digital input DI1:
Local control disabled.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Saves the valid parameter values into the permanent memory.
Saving completed
Saving in progress
Activates/deactivates alarms OVERCURRENT (code: A2001),
OVERVOLTAGE (code: A2002), UNDERVOLTAGE (code: A2003) and
DEVICE OVERTEMP (code: A2009). For more information, see chapter
Fault
tracing.
Alarms are inactive.
Alarms are active.
Selects the parameter view
Note: This parameter is visible only when it is activated by the optional
FlashDrop device. FlashDrop allows fast customisation of the parameter list,
e.g. selected parameters can be hidden. For more information, see
FlashDrop Manual.
FlashDrop parameter values are activated by setting parameter
APPLIC MACRO to OEM SET LOAD.
Complete long and short parameter lists
FlashDrop parameter list. Does not include short parameter list. Parameters
which are hidden by the FlashDrop device are not visible.
Frequency input signal processing. Digital input DI5 can be programmed as
a frequency input. Frequency input can be used as external reference signal
source. See parameter
1103/1106
Defines the minimum input value when DI5 is used as a frequency input.
Minimum frequency
Defines the maximum input value when DI5 is used as a frequency input.
Maximum frequency
REF1/2 SELECT.
Actual signals and parameters
79
0 = NOT SEL
0 = DONE
NO
0 = ABB
STANDARD
9902
0
1000