Detailed Explanation Of Setting Data - Mitsubishi Electric FX3G SERIES Programming Manual

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
34.5.1

Detailed explanation of setting data

Details on the setting data in the FLCMD instruction are as shown below.
Setting items
S
n
*1.
The CompactFlash
*2.
The CompactFlash
Cautions
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an
"FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Contents of instruction for operation
K0 to K63 : Forcibly writes the buffered data of the specified file ID to the CompactFlash
K-1 : Forcibly writes all buffered data to the CompactFlash
K256(H100) : Sets the CompactFlash
K512(H200) : Sets the CompactFlash
K1280(H500) : Clears error codes stored in the CF-ADP.
Channel number used by the CF-ADP
K1 : ch1
K2 : ch2
TM
card is available in the "mounted" status.
TM
card is unavailable in the "unmounted" status.
34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305
34.5 FNC 304 – FLCMD / FX3U-CF-ADP command
Description
TM
card.
TM
*1
card to the mounted status
.
TM
*2
card to the unmounted status
Data Type
TM
card.
16-bit binary
.
16-bit binary
751
31
32
33
34
35
36
37
38
A