FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Caution
• When using 32-bit counters (including 32-bit high-speed counters)
For comparing 32-bit counters and 32-bit high-speed counters (C200 to C255), make sure to use an instruction for
32-bit operation (DBKCMP=, DBKCMP>, DBKCMP<, DBKCMP<>, DBKCMP<=, or DBKCMP>=).
If an instruction for 16-bit operation (BKCMP=, BKCMP>, BKCMP<, BKCMP<>, BKCMP<=, or BKCMP>=) is used,
an operation error is caused (error code: K6705).
• Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction.
In the case of "DBKCMP = D0 D100 M0 R0", "n" is [R1, R0].
Errors
An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in
D8067.
• When the range of "n" ("2n" in 32-bit operation) points starting from
corresponding device range (error code: K6706)
• When the range of "n" points starting from
• When data registers starting from
from
S
(error code: K6706)
1
• When data registers starting from
from
S
(error code: K6706)
2
• When a 32-bit counter (C200 to C255) is specified in
For comparing 32-bit counters, make sure to use an instruction for 32-bit operation (DBKCMP=, DBKCMP>,
DBKCMP<, DBKCMP<>, DBKCMP<=, or DBKCMP>=).
25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare
D
exceeds the corresponding device range (error code: K6706)
D
specified as "D .b" overlap "n" ("2n" in 32-bit operation) points starting
specified as "D .b" overlap "n" ("2n" in 32-bit operation) points starting
D
S
and/or
1
25 Block Data Operation – FNC190 to FNC199
S
and/or
S
exceeds the
1
2
S
in 16-bit operation (error code: K6705)
2
21
22
23
24
25
26
27
28
29
30
611