4. Example of parallel recombination
Do not use MPS, MRD, MPP, ANB and ORB instructions in a program with branches and recombination.
Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions.
Pay attention to the programming order so that a branch line does not cross a recombination line.
<SFC program>
29
X010
9
50
<Step ladder>
X010
X011 X012
Before recombination, first program the drive processing of the state relays.
After that, program only the transfer processing to the recombination state relay.
5. Composition of branches and recombination
When a recombination line is directly connected to a branch line without a state relay as shown below, it is necessary
to provide a dummy state relay between the lines.
Create step ladder programs as shown below.
1)
Selective recombination and selective branch
<SFC program>
20
X000
1
100
Dummy state
X003
3
50
39
Y010
Y011
X011 X012
TRAN
STL
S29
Y010
STL
S39
Drive
Y011
processing
STL
S49
Y012
STL
S29
STL
S39
Transfer
processing
STL
S49
SET
S50
30
X001
2
TRAN
TRAN
X004
4
TRAN
TRAN
60
35 SFC Program and Step Ladder
49
Y012
<List program>
STL
S29
OUT
Y010
STL
S39
OUT
Y011
STL
S49
OUT
Y012
STL
S29
STL
S39
STL
S49
LD
X010
AND
X011
AND
X012
SET
S50
<Step ladder>
STL
S20
X000
SET
S100
STL
S30
X001
SET
S100
STL
S100
X003
SET
S50
X004
SET
S60
35.2 Step Ladder
31
32
33
34
35
36
37
<List program>
38
STL
S20
LD
X000
SET
S100
STL
S30
LD
X001
SET
S100
A
STL
S100
LD
X003
SET
S50
LD
X004
SET
S60
B