Error
PLC operation at
code
error occurrence
Operation error [M8067(D8067)]
0000
6701
6702
6703
6704
6705
6706
6707
6708
6709
Continues
operation
6710
6730
6732
6733
6734
6735
6736
6740
6742
6743
6744
6745
6746
6747
888
Contents of error
No error
No jump destination (pointer) for CJ or CALL
instruction
Label is undefined or out of P0 to P4095 due to
indexing
Label P63 is executed in CALL instruction; cannot be
used in CALL instruction as P63 is for jumping to
END instruction.
CALL instruction nesting level is 6 or more
Interrupt nesting level is 3 or more
FOR-NEXT instruction nesting level is 6 or
more.
Operand of applied instruction is inapplicable device.
Device number range or data value for operand of
applied instruction exceeds limit.
File register is accessed without parameter setting of file
register.
FROM/TO instruction error
Other (e.g. improper branching)
Mismatch among parameters
Incorrect sampling time (T
) (T
S
S
Incompatible input filter constant (α)
(α < 0 or 100 ≤ α)
Incompatible proportional gain (K
Incompatible integral time (T
) (T
I
Incompatible derivative gain (K
D
< 0 or 201 ≤ K
(K
)
D
D
Incompatible derivative time (T
D
) ≤ Scan time
Sampling time (T
S
Variation of measured value exceeds limit.
( PV < −32768 or +32767 <
Deviation exceeds limit.
(EV < −32768 or +32767 < EV)
Integral result exceeds limit.
(Outside range from −32768 to +32767)
Derivative value exceeds limit due to derivative gain
(K
).
D
Derivative result exceeds limit.
(Outside range from −32768 to +32767)
PID operation result exceeds limit.
(Outside range from −32768 to +32767)
This error occurs in the execution of operation. Review
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
This error occurs in the execution of operation.
Review the program and check the contents of the
operands used in applied instructions.
Verify that the specified buffer memories exist in the
counterpart equipment.
Verify that extension cables are correctly connected.
This error occurs in the execution of operation. Review
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
This error occurs when the same device is used within
the source and destination in a shift instruction, etc.
≤ 0)
<PID instruction is stopped.>
) (K
< 0)
P
P
This error occurs in the parameter setting value or
operation data executing PID instruction.
< 0)
I
Check the contents of the parameters.
)
) (T
< 0)
D
<Auto tuning is continued.>
The operation is continued in the condition "sampling
time (T
PV)
<PID operation is continued.>
The operation is continued with each parameter set to the
maximum and minimum value.
38 Error Check Method and Error Code List
38.4 Error Code List and Action
Action
) = cyclic time (scan time)".