for data model is modeled on the LD0\LLN0\NamPlt\configRev object. It is the most
important indicator of the configuration revision. Additionally, each Report Control
block has a confRev attribute that defines the revision and the DataSet of RCB. System
Consistency Check checks each LDs LLN0\NamPlt\configRev and confRev of each
RCB.
The GUI tool is divided into two tabs: the first tab gives an overview of the project with
the configuration consistency status of the IEDs. The second tab is used for setting the
options for the update procedure. Additionally, by clicking Details, a dialog on consist-
ency differences is shown.
Choose between the offline and online mode by selecting the corresponding radio button.
When the tool is started, it will automatically perform the offline check. In the offline
mode, the IED configuration revisions used in the SAB600 project are compared to the
specified IED configuration files. When the IED configuration file is imported to SAB600,
the file name and location are saved, and the information is later used by the System
Consistency Check tool. To enable the correct result of the comparison, always store the
changed configuration files with the same name to the same location as the originals. If
the location or the file name has changed, you can browse the new file with the Browse
button. If the configuration is inconsistent, click the Details button for more detailed
information.
In the online mode, configuration revisions are read from the IEDs and compared to the
current SAB600 project configuration. To use the online mode, the IEDs must be con-
nected to the same network with the computer running SAB600. After you have selected
the online mode, start the check by clicking the Start check button. Interrupt the check
by clicking the Stop Check button. For certain IEDs, it is possible to fetch the configur-
ation file from the IED, such as SPA-ZC 40x. To enable this, the FTP user and password
properties need to be correctly configured in the IED object.