ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB COM600 Series

  • Page 1 — COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual...
  • Page 3: Table Of Contents

    Abbreviations ................11 1.10. Related documents ..............12 1.11. Document revisions ..............12 Introduction ................... 13 2.1. General information about the COM600 series ......13 2.2. COM600 product series variants and rationale ......13 2.3. Functional overview ..............14 2.4.
  • Page 4 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.7.3. Controllable single point (SPC) for OPC internal data ..........28 3.4.7.4. Single point status (SPS) ......29 3.4.8. Configuring data objects ..........29 3.4.8.1. General information about configuring data objects ............
  • Page 5 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 5.2.9. Controllable double point (DPC) ........58 5.2.10. Device name plate (DPL) ..........59 5.2.11. Double point status (DPS) ..........59 5.2.12. Controllable integer status (INC) ........59 5.2.13.
  • Page 7: About This Manual

    Copyright This document and parts thereof must not be reproduced or copied without written per- mission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 8: Conformity

    (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 9: Document Conventions

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Operation This section covers the basic operation procedures you can carry out when transferring or activating Grid Automation Controller COM600 (later referred to as COM600) with new configurations.
  • Page 10: Terminology

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury.
  • Page 11: Abbreviations

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Term Description Event Change of process data or an OPC internal value. Normally, an event consists of value, quality, and timestamp. Intelligent Electronic Device A physical IEC 61850 device that behaves as its own commu- nication node in the IEC 61850 protocol.
  • Page 12: Related Documents

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Abbreviation Description Programmable Logic Controller Program Organization Unit Request To Send Substation Automation Substation Configuration Description Substation Configuration Language Sequential Function Chart Single Line Diagram eXtended Markup Language 1.10.
  • Page 13: Introduction

    DNP 3.0 Serial Master (OPC) User's Manual Introduction 2.1. General information about the COM600 series The COM600 product series are versatile Substation Management Units that help realize smart substation and grid automation solutions in industrial and utility distribution net- works.
  • Page 14: Functional Overview

    • COM600F is a dedicated distribution automation controller unit that runs dis- tributed grid and feeder applications for ANSI power networks and inherits all core features of the COM600 series. 2.3. Functional overview The DNP OPC Server provides methods for OPC clients to exchange data with devices communicating via the DNP protocol.
  • Page 15: Configuration

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Configuration 3.1. About this section This section guides you in the configuration tasks required before you can start using the DNP OPC Server. For information on the IEC 61850 data modeling, refer to COM600 User's Manual.
  • Page 16: Building Object Tree

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual In the object tree communication view, you can see the DNP OPC Server object and its child objects such as channels, devices, and data objects. After you have added the necessary objects to the object tree in the communication structure, configure them, see 3.4.1, General information about configuring objects.
  • Page 17: Adding Dnp Opc Server Object

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.3.3. Adding DNP OPC Server object After the Gateway object has successfully been added, you can continue building the object tree by adding DNP OPC Server object. To add DNP OPC Server object: 1.
  • Page 18: Adding Logical Device Objects

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual With SCL import function, you can import new objects with configurations from an existing file. Right-click the device and select SCL Import from the shortcut menu. To import a new configuration file: 1.
  • Page 19: Configuring Objects

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.4. Configuring objects 3.4.1. General information about configuring objects After the objects have been added, configure the object properties. Figure 3.4.1-1 shows an example of how to use SAB600 to configure the object properties for DNP OPC Server.
  • Page 20: Configuring Dnp Opc Server Properties

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.2. Configuring DNP OPC Server properties Table 3.4.2-1 DNP OPC Server properties Property/Parameter Value or Value range/Default Description Basic AE Prog ID Instance identification of dia- gnostic OPC alarm and event server.
  • Page 21 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/Parameter Value or Value range/Default Description Bit Rate 300 Bits/s Transmission rate used on the line. 600 Bits/s 1200 Bits/s 2400 Bits/s 4800 Bits/s 9600 Bits/s 19200 Bits/s...
  • Page 22 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/Parameter Value or Value range/Default Description Collision Detection Carrier detection not in use Defines of collision detection is in use or not. Carrier detection in use Default: Carrier detection not...
  • Page 23 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/Parameter Value or Value range/Default Description Only One Active Application True Specifies if only one application Layer Command Enabled layer command (e.g. poll) may False be active at any time. Enabling...
  • Page 24: Configuring Dnp Serial Device

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.4. Configuring DNP Serial Device Table 3.4.4-1 Configuring DNP Serial Device properties Name Value or Value range / Default Description Basic Diagnostics enabled True Diagnostics Enabled False Default: False...
  • Page 25 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Name Value or Value range / Default Description Pulse Length Off For Control 0 to 65535 Length of pulse, in milli- Relay Output Block seconds, used in the output Default: 0 commands of the control relay.
  • Page 26: Configuring Logical Device Properties

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Name Value or Value range / Default Description Process Data Confirmation Default: Disable Defines application level con- firmation handling. Lengths Application Message Data 0 to 5 Maximum number of retries of retries an application data fragment.
  • Page 27: Configuring Data Objects For Internal Opc Data

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/Parameter Value or Value range/ Default Description Logical Node Class ANCR, ARCO, ATCC, AVCO, Logical node class LPHD, CALH, CCGR, CILO, CPOW, CSWI, GAPC, GGIO, GSAL, IARC, IHMI, ITCI, ITMI,...
  • Page 28: Integer Status (Ins)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.7.2. Integer status (INS) Table 3.4.7.2-1 Property/Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850 Addresses Item Tag Path...
  • Page 29: Single Point Status (Sps)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.4.7.4. Single point status (SPS) Table 3.4.7.4-1 Configurable SPS (for OPC internal data) properties for OPC servers Property/Para- Value or Value range/ Default Description meter Basic Common Data...
  • Page 30 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter General Index 0...65535 General Index Default: 0 Neutral Index 0...65535 Neutral Index Default: 0 Phase A Index 0...65535 Phase A Index...
  • Page 31: Protection Activation Information (Act)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time And Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 32: Analog Set Point (Apc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Data Class Spe- cific Indication Object Binary input (1, 2) Object number for indication. Binary output (10) Default: Binary input (1, 2)
  • Page 33: Binary Counter Reading (Bcr)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Indication Index -1…65535 Indication index. Default: -1 Data Class Spe- cific Control Object Default: Analog control output Object number for control.
  • Page 34: Binary Controlled Step Position Information

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.8.6. Binary controlled step position information (BSC) Table 3.4.8.6-1 Configurable BSC properties Property/ Parameter Value or Value range/ Description Default Basic Common Data Class Common data class according to IEC 61850.
  • Page 35 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Sub-Type Subtype Simple MV sub-type Data Class Spe- cific Indication Object Analog input (30, 32) Object number for indication.
  • Page 36: Delta (Del)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.8.8. Delta (DEL) Table 3.4.8.8-1 Configurable DEL properties Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 37: Controllable Double Point (Dpc)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter High-High Default: 0 High-high limit for measurement. Event is created when value crosses the limit. Default: 0 Low limit for measurement. Event is cre- ated when value crosses the limit.
  • Page 38: Device Name Plate (Dpl)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send All Updates True Defines if all changes in value are sent to the master. False Default: False Send As Inverse...
  • Page 39: Double Point Status (Dps)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.4.8.11. Double point status (DPS) Table 3.4.8.11-1 Configurable DPS properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 40: Controllable Integer Status (Inc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time And Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 41: Integer Status (Ins)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.4.8.13. Integer status (INS) Table 3.4.8.13-1 Configurable INS properties Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 42: Measured Value (Mv)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 3.4.8.15. Measured value (MV) Table 3.4.8.15-1 Configurable MV properties Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 43: Controllable Single Point (Spc)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter High-High Default: 0 High-high limit for measurement. Event is created when value crosses the limit. Default: 0 Low limit for measurement. Event is cre- ated when value crosses the limit.
  • Page 44: Single Point Status (Sps)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send All Updates True Defines if all changes in value are sent to the master. False Default: False Send As Double True Defines if a value is sent as double point.
  • Page 45: Wye

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Update Rate 0...65535 Maximum update rate of signal state changes between the OPC server and Default: 0 client in milliseconds. 0 means that the server sends all the changes to the client.
  • Page 46 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Subtype WYE Simple Subtype of WYE Addresses Neutral Index -1 to 65535 Neutral Index Default: -1 Phase A Index...
  • Page 47 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Net Multiplier Default: Deka Specifies the multiplier for the current SI unit. Net Scale Default: None Scale for Net used with this data object.
  • Page 48: Event Definitions

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter High-High Default: 0 High-high limit for measurement. Event is created when value crosses the limit. Default: 0 Low limit for measurement. Event is cre- ated when value crosses the limit.
  • Page 49: Topic Generator

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 3.5. Topic Generator When the data objects have been configured with the DNP data objects, use the DNP Topic Generator function to specify how the data is requested from the DNP device.
  • Page 50 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual To add an event poll topic, specify the polling interval in hundreds of millisecond and the number of events to poll (Value 0 = all events). If you want to poll all events every 1 s, set up as shown in the Add Topic dialog.
  • Page 51 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual SAB600_DNP_Serial_Modify_Topic.png Figure 3.5-4 Modify an Existing Topic To delete a topic: In Topic Generator Tool, select whole row of the topic you want to delete. Press the Delete key from the keyboard to delete the topic.
  • Page 52: Operation

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Operation 4.1. About this section This section describes the basic operation procedures you can carry out after the server has been configured. After reading this section, you can, for example, monitor and control network connections.
  • Page 53: Dnp Channel Diagnostics

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 4.4. DNP channel diagnostics The DNP channel activity can be monitored with the Online diagnostics function. You can also take a channel into use or out of use as described in this section.
  • Page 54: Technical Reference

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Technical reference 5.1. About this section This section provides reference information about the following issues: • IEC 61850 data modeling • Attributes • Status codes 5.2. IEC 61850 data modeling 5.2.1.
  • Page 55: Protection Activation Information (Act)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field neut BOOLEAN state (0=OFF, VT_BOOL 1=ON) Quality DNP status VT_14 TimeStamp <server provided if VT_DATE none>...
  • Page 56: Binary Controlled Step Position Information (Bsc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Description VT_BSTR 5.2.5. Binary controlled step position information (BSC) Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field ctlVal ENUMERATED stop (0) | lower (1)
  • Page 57: Delta (Del)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 5.2.8. Delta (DEL) Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsAB. mag AnalogueValue Phase AB Current VT_R4 Value phsAB.q Quality VT_I4 on-line, com lost phsAB.t...
  • Page 58: Controllable Double Point (Dpc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsCA. mag AnalogueValue Phase CA Current VT_R4 Value phsCA.q Quality VT_I4 on-line, com lost phsCA.t TimeStamp VT_DATE phsCA.range...
  • Page 59: Device Name Plate (Dpl)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 5.2.10. Device name plate (DPL) Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field vendor VisibleString VT_BSTR hwRevision VisibleString VT_BSTR swRevision VisibleString VT_BSTR serNum...
  • Page 60: Controllable Enumerated Status (Enc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual 5.2.13. Controllable Enumerated Status (ENC) Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element ctlVal ENUMERATED Control Value VT_I4 stVal ENUMERATED Current value...
  • Page 61: Integer Controlled Step Position Information (Isc)

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 5.2.16. Integer controlled step position information (ISC) Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field ctlVal INTEGER -64 … 63 Control Code VT_I1...
  • Page 62: Controllable Single Point (Spc)

    COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field REAL VT_R4 siUnit Integer Config VT_I4 multiplier Integer Config VT_I4 unit String Config VT_BSTR numOfDec...
  • Page 63: Wye

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual 5.2.21. Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsA. mag AnalogueValue Phase A Current VT_R4 Value phsA.q Quality VT_I4 on-line, com lost phsA.t...
  • Page 64 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsC. mag AnalogueValue Phase C Current VT_R4 Value phsC.q Quality VT_I4 on-line, com lost phsC.t TimeStamp VT_DATE –...
  • Page 65 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element net.mag AnalogValue Net current value VT_R4 net.q Quality Online, com lost VT_R4 net.t Timestamp VT_DATE net.range...
  • Page 66: Device Profile

    Table A1-1 The device profile describing the implementation of the DNP 3.0 master protocol in COM600 DNP 3.0 DEVICE PROFILE DOCUMENT Vendor Name: ABB Oy Distribution Automation Device Name: COM600 3.4 Highest DNP Level Supported: Device Function: For Requests: Subset Level 2...
  • Page 67 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Requires Data Link Layer Confirmation: [ ] Never [ ] Always (not recommended) [ ] When reporting Event Data (Slave devices only) [ ] When sending multi-fragment responses (Slave devices only) [ ] Sometimes.
  • Page 68 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Requires Data Link Layer Confirmation: Pulse Off [ ] Never [ ] Always [ ] Sometimes [x] Configurable Latch On [ ] Never [ ] Always [ ] Sometimes [x] Configurable...
  • Page 69 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Code Function Description Supported Direct operate Set the output directly Respond with status of control point Direct operate - no Set the output directly No respond Freeze Function Codes...
  • Page 70 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Code Function Description Supported Save configuration Save the configuration Respond with status of operation Enable Unsolicited Enable Unsolicited Messages Messages Respond with status of operation Disable Unsolicited Disable Unsolicited Messages...
  • Page 71 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Data object Variation Description Function code Qualifier code Function code Qualifier code type of Request of Request of Response of Response message message message message Binary input 6,7,8...
  • Page 72 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Data object Variation Description Function code Qualifier code Function code Qualifier code type of Request of Request of Response of Response message message message message 16-bit frozen 129,130...
  • Page 73 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Data object Variation Description Function code Qualifier code Function code Qualifier code type of Request of Request of Response of Response message message message message 16-bit analog 3,4,5,6...
  • Page 75: Index

    1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Index activation information properties ....................... 31 adding Data object ..................... 18 Gateway object ....................16 Logical device ....................18 Logical node ....................18 OPC Server object ..................17 analog set point properties .......................
  • Page 76 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Data object adding ......................18 data object configuring ..................... 29 Delta (DEL) IEC 61850 data modeling ................57 properties ....................... 36 device communication monitoring and controlling ................53 device name plate properties .......................
  • Page 77 1MRS756567 COM600 series, Version 5.0 DNP 3.0 Serial Master (OPC) User's Manual Integer controlled step position information (ISC) IEC 61850 data modeling ................61 Integer status (INS) IEC 61850 data modeling ................60 properties ....................28, 41 Logical device adding ......................18 Logical Device properties .......................
  • Page 78 COM600 series, Version 5.0 1MRS756567 DNP 3.0 Serial Master (OPC) User's Manual Logical Node ....................26 logical node name plate .................. 41 Measured value (MV) ..................42 Single point status (SPS) ................29, 44 WYE ......................45 Protection activation information (ACT) IEC 61850 data modeling ................
  • Page 80 Fax. +358 10 224 1094 ABB Inc. Medium Voltage Products 655 Century Point Lake Mary, FL 32746, USA Tel: +1 407 732 2000 Fax: +1 407 732 2335 www.abb.com/medium-voltage 1MRS756567 H/24.5.2017 © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents