ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB COM600 Series

  • Page 1 — COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual...
  • Page 3: Table Of Contents

    Abbreviations ................11 1.10. Related documents ..............12 1.11. Document revisions ..............12 Introduction ................... 14 2.1. General information about the COM600 series ......14 2.2. COM600 product series variants and rationale ......14 2.3. Functional overview ..............15 2.4.
  • Page 4 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5.7. Complex measured value (CMV) ....34 3.4.5.8. Delta (DEL) ..........35 3.4.5.9. Controllable double point (DPC) ....37 3.4.5.10. Double point status (DPS) ......38 3.4.5.11. Controllable integer status (INC) ....40 3.4.5.12.
  • Page 5 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.3.2. Link layer status codes ..........64 5.3.3. Application layer status codes ........64 5.4. Attributes ..................65 5.4.1. General information about attributes ......65 5.4.2. DNP Serial Slave OPC Client attributes ....... 65 5.4.3.
  • Page 7: About This Manual

    Copyright This document and parts thereof must not be reproduced or copied without written per- mission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 8: Conformity

    (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 9: Document Conventions

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Configuration In this section you find an overview of the configuration tasks and instructions on how to create and configure DNP Serial Slave OPC Client related objects. Operation This section covers the basic operation procedures you can carry out when transferring or activating the COM600 computer with new configurations.
  • Page 10: Use Of Symbols

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual MIF349 • Variables are shown using lowercase letters: sequence name 1.7. Use of symbols This publication includes warning, caution, and information icons that point out safety- related conditions or other important information. It also includes tip icons to point out useful information to the reader.
  • Page 11: Abbreviations

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Term Description Data Access; DA An OPC service for providing information about process data to OPC clients. Data Object; DO Part of a logical node object representing specific information, for example, status, or measurement.
  • Page 12: Related Documents

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Abbreviation Description International Electrotechnical Commission Intelligent Electronic Device Local Area Network Logical Device Logical Node Network Control Center Object Linking and Embedding OLE for Process Control P&C Protection & Control...
  • Page 13 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Document version/date Product revision History G/30.6.2011 Document revised H/31.5.2012 Document revised K/13.3.2015 Document revised L/24.5.2017 Document revised...
  • Page 14: Introduction

    DNP 3.0 Serial Slave (OPC) User's Manual Introduction 2.1. General information about the COM600 series The COM600 product series are versatile Substation Management Units that help realize smart substation and grid automation solutions in industrial and utility distribution net- works.
  • Page 15: Functional Overview

    • COM600F is a dedicated distribution automation controller unit that runs dis- tributed grid and feeder applications for ANSI power networks and inherits all core features of the COM600 series. 2.3. Functional overview The DNP protocol slave interface of COM600 enables master systems communicating with DNP protocol to receive data from and deliver commands to P&C devices connected...
  • Page 16: Configuration

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Configuration 3.1. About this section This section guides you in the configuration tasks required before you can start using the DNP Serial Slave OPC Client. For information on the IEC 61850 data modeling, refer to COM600 User's Manual.
  • Page 17 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual SAB600_DNP_Serial_Slave_Example_View.png Figure 3.2-1 Example view of SAB600 The configuration work can basically be divided into two separate tasks: 1. building an object tree, and 2. configuring object properties.
  • Page 18: Building Object Tree

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Object Description DNP Serial IED A DNP Serial IED is used for a virtual station in COM600 representing the slave stations visible to the DNP master system. Data Object (DO)
  • Page 19: Adding Channel Objects

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 1. Add the DNP Serial Slave OPC Client object in the Communication structure by selecting the Gateway object. 2. Right-click the Gateway object and select New > DNP > DNP Serial Slave OPC Client.
  • Page 20: Configuring Objects

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 4. Drag and drop the logical node into the Cross-References function. The data objects within the logical node appear now in the Cross-References function. Note that only data objects that have been given a non zero information address in the Cross-References table will be connected to the DNP Serial IED.
  • Page 21: Configuring Dnp Serial Slave Opc Client Properties

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Clicking Save connects the data objects to the DNP Serial IED. After clicking Save the connected data objects appears as child objects for the respective DNP Serial IED. The cross reference information can then be also modified by selecting the data object and using the object properties window.
  • Page 22: Configuring Dnp Serial Channel Properties

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter Station/Remote Reject commands if position Defines command handling if the position Switch Error bad or unknown. is bad or unknown.
  • Page 23 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter Bit Rate 300 bits/s Transmission rate used on the channel. 600 bits/s 1200 bits/s 2400 bits/s 4800 bits/s...
  • Page 24 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter CTS Delay 0...65535 Time delay in milliseconds between the activation of the RTS signal and the start Default: 0 of a new transmission.
  • Page 25: Configuring Dnp Serial Ied Properties

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.4. Configuring DNP Serial IED properties Table 3.4.4-1 lists the configurable properties for DNP Serial IED and value ranges for these properties. The actual configuration by using the SAB600 is performed as described in 3.2, Overview of configuration.
  • Page 26 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Name Value/Value range Description Command Hand- ling Command Address 0...65535 The object address of the bitstream pro- cess object. Default: 32000 Execute Waiting 0...600 The maximum time in seconds that the...
  • Page 27: Configuring Data Objects

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5. Configuring data objects 3.4.5.1. General information about configuring objects After the objects have been added, configure the object properties. Figure 3.4.5.1-1 shows an example of how to use SAB600 to configure the object properties for DNP OPC Server.
  • Page 28: Directional Protection Activation Information (Acd)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5.2. Directional protection activation information (ACD) Table 3.4.5.2-1 Configurable ACD properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 29: Protection Activation Information (Act)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send As Double True Defines if a value is sent as double point. Point False Default: False Send As Inverse...
  • Page 30 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Common Class Class 0...3 Class of ASDU. Data sent from the slave to the master can be assigned to four Default: Class 0 classes.
  • Page 31: Analog Set Point (Apc)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5.4. Analog set point (APC) Table 3.4.5.4-1 Configurable APC properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
  • Page 32: Binary Counter Reading (Bcr)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time and Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 33: Binary Controlled Step Position Information (Bsc)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send As 16 Bit Send as 32 bit value Defines if the value is sent as 16 or 32 bit Value value.
  • Page 34: Complex Measured Value (Cmv)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Parameter Value or Value range/ Description Default Control Object Default: Analog control Object number for control. output block (41). Indication Object Analog input (30, 32) Object number for indication.
  • Page 35: Delta (Del)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Class Class 0...3 Class of ASDU. Data sent from the slave to the master can be assigned to four Default: Class 3 classes.
  • Page 36 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Common Data Common data class according to IEC Class 61850. Addresses Phase AB Index 0...65535 Phase AB Index Default: 0 Phase BC Index 0...65535...
  • Page 37: Controllable Double Point (Dpc)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time And Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 38: Double Point Status (Dps)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Indication Object Binary input (1, 2) Object number for indication. Binary output (10) Default: Binary input (1, 2) Send All Updates...
  • Page 39 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Class Class 0...3 Class of ASDU. Data sent from the slave to the master can be assigned to four Default: Class 0 classes.
  • Page 40: Controllable Integer Status (Inc)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5.11. Controllable integer status (INC) Table 3.4.5.11-1 Configurable INC properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC...
  • Page 41: Integer Status (Ins)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time And Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 42: Integer Controlled Step Position Information

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send As 16 Bit Send as 32 bit value Defines if the value is sent as 16 or 32 bit Value value.
  • Page 43: Measured Value (Mv)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Indication Object Analog input (30, 32) Object number for indication. Analog output (40) Default: Analog input (30, 32) Send All Updates...
  • Page 44: Controllable Single Point (Spc)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Update Rate 0...65535 Maximum update rate of signal state changes between the OPC server and Default: 1000 client in milliseconds. 0 means that the server sends all the changes to the client.
  • Page 45 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Control Index 0...65535 Control index. Default: 0 Indication Index 0...65535 Indication index. Default: 0 Common Class Class 0...3 Class of ASDU. Data sent from the slave...
  • Page 46: Single Point Status (Sps)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Time And Type Send as static data (always Specifies the type of the timestamp a Variation without time) message is sent with.
  • Page 47: Wye

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Send As Double True Defines if a value is sent as double point. Point False Default: False Send As Inverse...
  • Page 48 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property/ Para- Value or Value range/ Default Description meter Res Index 0...65535 Res Index Default: 0 Common Class Class 0...3 Class of ASDU. Data sent from the slave...
  • Page 49: Controllable Enumerated Status (Enc)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 3.4.5.18. Controllable Enumerated Status (ENC) Table 3.4.5.18-1 Configurable ENC properties for OPC client Property/Parameter Value or Value range/ Default Description Basic Common Data Class Common data class according to IEC 61850.
  • Page 50: Enumerated Status (Ens)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Time and Type Variation Send as static data (always Specifies the type of the without time) timestamp a message is sent with. Event without time Event with time...
  • Page 51 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Send As 16 Bit Value Send as 32 bit value Defines if the value is sent as 16 or 32 bit value. Send as 16 bit value Default: Send as 16 bit value...
  • Page 52: Operation

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Operation 4.1. About this section This section describes the basic operation procedures you can carry out after the object properties for the DNP Serial Slave OPC Client have been configured.
  • Page 53: Dnp Serial Channel Diagnostics

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual A040308.jpg Figure 4.3-2 Event log file 4.4. DNP Serial Channel diagnostics The DNP Serial Channel activity can be monitored with the Online diagnostics function. You can also take a channel into use or out of use as described in this section.
  • Page 54: Signal Diagnostics

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual You can take a DNP Serial IED into use by marking the In use check box. If you unmark the check box, the device is taken out of use. To manually update diagnostic counters, click Refresh.
  • Page 55 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Right-click the DNP Serial Slave OPC Client. Select Diagnostic AE client (see Figure 4.6-1) A040338.jpg Figure 4.6-1 DNP Serial Slave OPC Client Diagnostic AE client Detailed information about field values (ASDU types, qualifier values and so on) can...
  • Page 56: Technical Reference

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Technical reference 5.1. About this section This section provides reference information about the following issues: • IEC 61850 data modeling • Attributes • Status codes 5.2. IEC 61850 data modeling 5.2.1.
  • Page 57: Double Point Status (Dps)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.3. Double point status (DPS) Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element stVal ENUMERATED Intermediate-state state (0=OFF, VT_I4 1=ON) off (1)
  • Page 58: Protection Activation Information (Act)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.6. Protection activation information (ACT) ACT phases information is mapped in the same way as SPS stVal. Name Type Value/ Value Mandat- Protocol informa- OPC data types range...
  • Page 59: Binary Counter Reading (Bcr)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.8. Binary counter reading (BCR) Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element actVal INTEGER Value | Frozen VT_I4 value | Current...
  • Page 60: Wye

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.11. Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element phsA.cVal.mag AnalogueValue Phase A Current VT_R4 Value phsA.q Quality VT_I4 DNP status phsA.t...
  • Page 61: Delta (Del)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.12. Delta (DEL) Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element phsAB. cVal.mag t AnalogueValue Phase AB Current VT_R4 Value phsAB.q Quality...
  • Page 62: Controllable Integer Status (Inc)

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element ctlSelOff FALSE | TRUE Control Code VT_BOOL stVal ENUMERATED intermediate-state State (0=OFF, VT_I4 1=ON)
  • Page 63: Binary Controlled Step Position Information (Bsc)

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.2.17. Binary controlled step position information (BSC) Name Type Value/ Value Mandat- Protocol informa- OPC data types range ory/Optional tion element ctlVal ENUMERATED stop (0) Control Value VT_I1...
  • Page 64: Link Layer Status Codes

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 5.3.2. Link layer status codes 17650 The Data Flow Control ( DFC) bit of the messages from the master is set for more than 15 seconds. 17651 The DCD or CTS signal or the end of the transmitted message is not received in correct time.
  • Page 65: Attributes

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual 5.4. Attributes 5.4.1. General information about attributes In addition to item tags for process data (indications and commands), the OPC servers and clients also provide some item tags for controlling the devices and retrieving status information from them.
  • Page 66: Dnp Serial Channel Attributes

    COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual 5.4.3. DNP Serial Channel attributes Table 5.4.3-1 DNP Serial Channel attributes Property / Para- Value or Value range/ Default Description meter In Use 0 = Not in use, the channel...
  • Page 67: Dnp Serial Ied Attributes

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter Failed Transmis- The number of failed transmissions. sions Transmitted Com- The number of transmitted commands. mands Transmitted Replies The number of transmitted replies.
  • Page 68 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter Object Status When written: Data type: Integer 1 = Re-transmit system mes- Access: No limitations sage Indicates the detailed information about When read: the station device status.
  • Page 69 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Property / Para- Value or Value range/ Default Description meter Queue Diagnostics Data type: Integer Access: No limitations Size of APDU in- queue Size of APDU out- queue...
  • Page 70: Device Profile

    Table A1-1 Device profile describing the implementation of DNP V3.00 slave pro- tocol in COM600 SUBSET 2: the default subset DNP V3.00DEVICE PROFILE DOCUMENT Vendor Name: ABB Oy Substation Automation Products Device Name: COM600 Highest DNP Level Supported: For Requests: Subset Level 2...
  • Page 71 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Requires Data Link Layer Confirmation: [x] Configurable Timeouts while waiting for: Data Link Confirm [ ] None [ ] Fixed at _________ [ ] Variable [x] Configurable Complete Appl. Fragment...
  • Page 72 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Sends/Executes Control Operations: Latch Off [ ] Never [x] Always [ ] Sometimes [ ] Configurable Queue [x] Never [ ] Always [ ] Sometimes [ ] Configurable...
  • Page 73 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Table A1-2 Supported function codes CODE FUNCTION DESCRIPTION Supported Transfer Function Codes Confirm Message fragment confirmation No response Read Request objects from outstation Respond with requested objects Write Store the specified objects to out- station.
  • Page 74 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual CODE FUNCTION DESCRIPTION Supported Freeze with time Copy the specified objects to freeze buffer at specified time Respond with status of operation Freeze with time Copy the specified objects to...
  • Page 75 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual CODE FUNCTION DESCRIPTION Supported Delay Measure- Perform propagation delay meas- ment urement Record current Used in a network application to time allow the Master station and the Outstation to record their time at...
  • Page 76 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) Control Block - All Variations Control Relay 3, 4, 5, 6...
  • Page 77 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 32-Bit Frozen Counter with Time of Freeze 16-Bit Frozen...
  • Page 78 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 16-Bit Delta Counter Change Event without Time 32-Bit Counter...
  • Page 79 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 16-Bit Frozen Delta Counter Event with Time Analog Input -...
  • Page 80 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 32-Bit Analog 129,130 17,28 Change Event without Time...
  • Page 81 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) Time and Date - All Variations Time and Date...
  • Page 82 Table A1-4 Device profile describing the implementation of DNP V3 slave protocol in COM600 SUBSET 3: the used subset is selected using the IED's subset property DNP V3.00DEVICE PROFILE DOCUMENT Vendor Name: ABB Oy Substation Automation Products Device Name: COM600 Highest DNP Level Supported:...
  • Page 83 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual DNP V3.00DEVICE PROFILE DOCUMENT Maximum Data Link Re-tries: Maximum Application Layer Re-tries: [ ] None [ ] None [ ] Fixed at _______________________ [x] Configurable, range 0 to 10...
  • Page 84 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual Timeouts while waiting for: Sends/Executes Control Operations: WRITE Binary Outputs [x] Never [ ] Always [ ] Configurable [ ] Sometimes SELECT/OPERATE [ ] Never [x] Always [ ] Configurable...
  • Page 85 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Timeouts while waiting for: [x] Never [ ] Always [ ] Configurable [ ] Sometimes FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY: Reports Binary Input Change Events when no specific...
  • Page 86 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual CODE FUNCTION DESCRIPTION Supported Read Request objects from outstation Respond with requested objects Write Store the specified objects to out- station. Respond with status of operation Control Function Codes...
  • Page 87 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual CODE FUNCTION DESCRIPTION Supported Application Control Function Codes Cold Restart Perform desired reset sequence Respond with a time object Warm Restart Perform desired partial reset oper- ation Respond with a time object...
  • Page 88 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual CODE FUNCTION DESCRIPTION Supported Confirm Message fragment confirmation Response Response to requested message Unsolicited Mes- Spontaneous message without sage request Supported objects Table A1-6 Supported objects OBJECT Description...
  • Page 89 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) Binary Counter - 1, 7, 8, 9, 10, 22...
  • Page 90 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 32-Bit Frozen Delta Counter with Time of Freeze...
  • Page 91 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 16-Bit Counter Change Event with Time 32-Bit Delta...
  • Page 92 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 16-Bit Analog 00,01,06 129, 130 00, 01 Input...
  • Page 93 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) 16-Bit Analog Change Event with Time Frozen Analog...
  • Page 94 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) Unsynchronized 129, 130 quantity=1 Time and Date Time Delay - All...
  • Page 95 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual OBJECT Description REQUEST Qual RESPONSE Qual Codes (slave must Codes(hex) (master must (hex) parse) parse) Func Codes Func Codes (dec) Small Packed Binary-Coded Decimal Medium Packed Binary-Coded Decimal...
  • Page 97: Index

    1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Index activation information properties ....................... 29 adding channel object ....................19 data object ..................... 19 device object ....................19 OPC client ...................... 18 analog set point properties ....................... 31 application layer ....................
  • Page 98 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual properties ....................... 40 Controllable single point (SPC) IEC 61850 data modeling ................61 properties ....................... 44 data object adding ......................19 configuring ..................... 20 Delta (DEL) IEC 61850 data modeling ................61 properties .......................
  • Page 99 1MRS755495 COM600 series, Version 5.0 DNP 3.0 Serial Slave (OPC) User's Manual Double point status (DPS) ................57 Integer status (INS) ..................57 Measured value (MV) ..................59 Protection activation information (ACT) ............58 Single point status (SPS) ................56 WYE ......................
  • Page 100 COM600 series, Version 5.0 1MRS755495 DNP 3.0 Serial Slave (OPC) User's Manual OPC client ...................... 21 Single point status (SPS) ................46 WYE ......................47 Protection activation information (ACT) IEC 61850 data modeling ................58 signal diagnostics ..................... 54 Single point status (SPS) IEC 61850 data modeling ................
  • Page 104 Fax. +358 10 224 1094 ABB Inc. Medium Voltage Products 655 Century Point Lake Mary, FL 32746, USA Tel: +1 407 732 2000 Fax: +1 407 732 2335 www.abb.com/medium-voltage 1MRS755495 L/24.5.2017 © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.