ABB TZIDC Operating Instructions Manual page 49

Electro-pneumatic positioner
Table of Contents

Advertisement

Electrical data
Signal circuit
(Terminal +11 / -12)
Contact input
(Terminal +81 / -82)
Switch output
(Terminal +83 / -84)
Mechanical digital feedback
(Terminals Limit1 +51 / -52
or Limit2 +41 / -42)
Plug-in module for digital
position feedback
(Terminal +51 / -52) or
+41 / -42)
Plug-in module for analog
position feedback
(Terminal +31 / -32)
Plug-in module for shutdown
contact input
(Terminal +51 / -52) or
+85 / -86)
Local communication
interface (LKS)
IMPORTANT (NOTE)
The local communication interface (LKS) may only be operated at Um ≤ 30 V DC outside
the potentially explosive area.
The equipment may only be used as a II 2 D type device in areas where the level of
mechanical danger is "low".
42/18-84-EN
In intrinsically safe explosion protection types
Ex ib IIC / Ex ia IIC or Ex iaD, only for connection to a certified
intrinsically safe circuit
Maximum values:
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 6.6 nF
i
L
negligibly small
i
Maximum values:
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 4.2 nF
i
L
negligibly small
i
Maximum values:
U
= 30 V
i
I
= 320 mA
i
P
= 500 mW
i
C
= 4.2 nF
i
L
negligibly small
i
For max. values, see EC-type-examination test certificate
number PTB 00 ATEX 2049 X
Proximity switches manuf. by Pepperl & Fuchs
Maximum values:
U
= 30 V
i
I
= 320 mA
i
P
= 500 mW
i
C
= 3.7 nF
i
L
negligibly small
i
Maximum values:
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 6.6 nF
i
L
negligibly small
i
U
= 30 V
i
I
= 320 mA
i
P
= 1.1 W
i
C
= 3.7 nF
i
L
negligibly small
i
Only for connection to a programmer outside the potentially
explosive area.
TZIDC, TZIDC-110, TZIDC-120
Ex relevant specifications
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-120Tzidc-110

Table of Contents