Specifications
9.3.2

Device name

Device name
Dev. ID
9.3.3

Output

Range
Air capacity
at 1.4 bar (20 psi)
supply pressure
at 6 bar (90 psi)
supply pressure
Output function
Shut-off values
9.3.4

Travel

Ste
Rotation angle
Used range
25 ... 120°
rotary actuators, optionally 270°
25 ... 60°
linear actuators
Travel time
prolongation
Setting range
0 ... 200 seconds, separately for each
direction
9.3.5

Air supply

Instrument air
Supply pressure
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Air consumption
46
ABB TZID-C120-TAG
0003200028-TZID-C120XXXXXXXXXX
0 ...6 bar (0 ... 90 psi)
3
5.0 kg/h = 3.9 Nm
/h=2.3 scfm
3
13 kg/h = 10 Nm
/h = 6.0 scfm
For single or double-acting actuators,
air is vented from actuator or actuator
is blocked in case of (electrical) power
failure
End Position 0 %
= 0 ... 45 %
End position 100 % = 55 ... 100 %
free of oil, water and dust to DIN/ISO
8573-1. Pollution and oil content
according to Class 3 (purity: max.
particle size = 5 µm, max. particle density
3
= 5 mg / m
; oil content: max.
3
concentration = 1 mg / m
; pressure dew
point: 10 K below operating temperature)
1.4 ... 6 bar (20 ... 90 psi)
< 0.03 kg/h / 0.015 scfm (independent
of supply pressure)
TZIDC, TZIDC-110, TZIDC-120
9.3.6

Transmission data and influences

Direction of action (output signal or pressure in actuator)
Increasing
Increasing output signal 0 ... 100 %
Increasing pressure y1 in the actuator
Decreasing
Increasing output signal 0 ... 100 %
Decreasing pressure y1 in the actuator
Characteristic deviation
Tolerance band
Dead band
Resolution (A/D conversion)
Sample rate
Influence of ambient
temperature
Influence of vibration
Seismic requirements
Meets requirements of DIN / IEC 68-3-3 Class III for strong and
strongest earthquakes.
Influence of mounting orientation
Not measurable.
Meets the requirements of the following directives
-
EMC Directive 2004/108/EC as of December 2004
-
EC Directive for CE conformity marking
9.3.7

Environmental capabilities

Ambient temperature
For operation, storage and transport:
When using proximity switches
SJ2-S1N (NO):
Relative humidity
Operational (with closed housing
and air supply switched on):
Transport and storage:
< 0.5 %
0.3 ... 10 %, adjustable
0.1 ... 5 %, adjustable
> 16000 steps
20 ms
< 0.5 % for each 10 K
< ± 1 % to 10 g and 80 Hz
-40 ... 85 °C (-40 ... 185 °F)
-25 ... 85 °C (-13 ... 185 °F)
95 % (annual average),
condensation permissible
75 % (annual average), non-
condensing
42/18-84-EN