9.1.5

Transmission data and influences

Output Y1
Increasing
Increasing setpoint signal 0 ... 100 %
Increasing pressure at output
Decreasing
Increasing setpoint signal 0 ... 100 %
Decreasing pressure at output
Action (setpoint signal)
Increasing
Signal 4 ... 20 mA = actuator position 0 ... 100 %
Decreasing
Signal 20 ... 4 mA = actuator position 0 ... 100 %
Characteristic curve (travel = f {setpoint signal})
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 and freely
configurable with 20 reference points.
Deviation
Tolerance band
Dead band
Resolution (A/D conversion)
Sample rate
Influence of ambient temperature
Influence of vibration
Seismic vibration
Meets requirements of DIN / IEC 68-3-3 Class III for strong and
strongest earthquakes.
Influence of mounting orientation
Not measurable.
Complies with the following directives
-
EMC Directive 2004/108/EC as of December 2004
-
EC Directive for CE conformity marking
Communication
-
HART Protocol 5.9
-
Local connector for LKS (not in Ex area)
-
HART communication via 20 mA signal line with (optional) FSK
modem
9.1.6

Environmental capabilities

Ambient temperature
For operation, storage and transport:
When using proximity switches
SJ2-S1N (NO):
Relative humidity
Operational (with closed housing
and air supply switched on):
Transport and storage:
42/18-84-EN
< 0,5 %
0.3 ... 10 %, adjustable
0.1 ... 10 %, adjustable
> 16000 steps
20 ms
< 0.5 % per 10 K
< 1 % to 10 g and 80 Hz
-40 ... 85 °C (-40 ... 185 °F)
-25 ... 85 °C (-13 ... 185 °F)
95 % (annual average),
condensation permissible
75 % (annual average), non-
condensing
TZIDC, TZIDC-110, TZIDC-120
9.1.7

Housing

Material / Degree of protection
Aluminum, protection class IP 65 (optional IP 66) / NEMA 4X
Surface / Color
Electrostatic dipping varnish with epoxy resin, stove-hardened.
Case varnished black, RAL 9005, matte, housing cover Pantone
420.
Electrical connections
Screw terminals:
Max. 1.0 mm
Max. 2.5 mm
4 ... 20 mA input signal
IMPORTANT (NOTE)
Do not expose the terminals to strain.
Four thread combinations for cable entry and pneumatic
connection
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
(Optional: With cable gland(s) and pipe plugs if necessary)
Weight
1,7 kg (3,75 lb)
Mounting orientation
Any
9.1.8

Safety Integrity Level

IMPORTANT (NOTE)
Applies to applications with single-acting and depressurizing
pneumatics.
The positioner TZIDC / TZIDC-200 and the emergency shutdown
module for meet the requirements regarding:
-
functional safety acc. to IEC 61508
-
explosion protection (depending on the model)
-
electromagnetic compatibility in accordance with EN 61000
Without the input signal, the pneumatic module in the positioner vents
the drive and the installed spring in it moves the valve in a
predetermined end position (OPEN or CLOSED).
SIL specific safety-related characteristics:
Device
SFF
TZIDC / TZIDC-200 as
94 %
shutdown module
TZIDC / TZIDC-200 with
94 %
supply current 0 mA
For details refer to the Management Summary in the SIL-Safety
Instructions 37/18-79XA.
Specifications
2
(AWG 17) for options
2
(AWG 14) for
PFDav
λ
+ λ
λ
dd
s
du
-4
718 FIT
40 FIT
1.76 * 10
1.76 * 10
-4
651 FIT
40 FIT
41