Mitsubishi Electric AG-150A Instruction Book page 46

Air-conditioner control system centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

(3) Edit the patterns.
Refer to 6-3-1 (3) for the figure of LOSSNAY,
Air To Water (PWFY), general equipment, and HWHP
(4) Assign schedule patterns to special dates.
(5) Copy a schedule to another pattern or to another group
Refer to the figures under 6-3-1 (4) for how to copy
the schedule of one group to another.
(Air Conditioner)
(CAHV) .
Date button
After selecting the pattern, touch the schedule content button to bring
up the schedule content setting screen. Make the settings for the
execution time and operation patterns (ON/OFF, operation mode,
setting temperature, airflow direction, fan speed, remote controller
operation prohibition) on the schedule content setting screen, and
then touch the [OK] button. Not all settings need to be made. The
settings for only the operation mode or the setting temperature, for
example, can be made.
Note: When setting a schedule for all groups or for a block, it is
possible to set all operation modes such as Auto mode etc, but
if some targeted air conditioner units do not have such a
function, then those units will not run in the specified mode.
When setting the schedule, consider what functions are
supported by the air conditioner units.
Note: When setting a schedule for all groups or for a block, it is
possible to set prohibit remote controller items individually.
When allowing remote controller operation under K control,
however, all items must be set enable.
Note: Configurable settings depend on the type of group (Air
Conditioner group, LOSSNAY group, Air-To-Water (PWFY)
group, general equipment group, and HWHP (CAHV) group).
Note: When setting a schedule for ventilator units, the temperature
setting is not displayed. Moreover, the prohibit remote
controller operation is simply [ON/OFF].
Note: Only the ON/OFF operation is possible on the general
equipment.
Assign the schedule patterns to the dates to which regular weekly
schedule does not apply, such as holidays and summer break.
Touch the desired date on the calendar to see which pattern is
assigned to the date. Each touching of the button will cycle through
the letters ABCDE and blank, then back to A. Touch the button until
you get the pattern you want. Select blank to cancel the selection.
To copy a pattern to another, select the pattern from the pattern menu
on the schedule pattern setting screen, touch [Copy] to select it, select
a pattern to copy to, and touch [Paste].
To copy the annual schedule for one group to another group, select
the group from the annual schedule setting screen (Floor layout or
block display screen), touch [Copy], select a group to copy the
schedule to, and touch [Paste].
* The settings of one type of equipment cannot be copied to the
settings of a different type of equipment. (i.e., The settings of air
conditioning units cannot be copied to ventilation equipment
(LOSSNAY) settings.)
* Available operation modes and setting temperature range varies
with models.
– 45 –

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ag-150a-a