• Optimized start-up schedule function
Optimized start-up schedule function is a function that starts an air conditioning unit 5 - 60 minutes prior in order to reach the scheduled
temperature at the scheduled time.
Note: A unit starts 30 minutes prior at the first boot.
Note: If the room temperature is measured by the air-conditioner's suction temperature sensor, the temperature may not be correct
when the air-conditioner is inactive and the air is not fresh. When the temperature is not measured correctly, switch the sensor to
external temperature sensor (PAC-SE40TSA) or remote control sensor.
26°C/79°F
Ex.) Pre-cooling (Setting 9:00 26°C/79°F)
Select the mode [Optimized Start] on the schedule setting screen when this function is required.
[Operation] [Cooling]
26°C/79°F
Room
temperature
8:45
9:00
24°C/75°F
[Operation] [Heating]
24°C/75°F
8:40
Ex.) Pre-heating (Setting 9:00 24°C/75°F)
– 40 –
Room
temperature
9:00