(3) Select the day of the week
Schedule content button
(4) Set the contents of the schedule
Refer to 6-3-1 (3) for the figure of LOSSNAY,
Air To Water (PWFY), general equipment, and HWHP
(5) Copy a schedule to another day of the week or to another group
Refer to the figures under 6-3-1 (4) for how to copy
the schedule of one group to another.
(Air Conditioner)
(CAHV).
Select the days of a week from the weekly schedule screen and touch
the schedule content button to bring up the schedule content setting
screen.
Note: When multiple groups are selected, those settings that have
been made for each group will not be displayed.
Press [OK] to delete the schedule, or press [Cancel] to exit the
screen without saving any changes.
Make the settings for the execution time and operation patterns (ON/
OFF, operation mode, setting temperature, airflow direction, fan
speed, remote controller operation prohibition) on the schedule
content setting screen, and then touch the [OK] button. Not all settings
need to be made. The settings for only the operation mode or the
setting temperature, for example, can be made.
Note: When setting a schedule for all groups or for a block, it is
possible to set all operation modes such as Auto mode etc, but
if some targeted air conditioner units do not have such a
function, then those units will not run in the specified mode.
When setting the schedule, consider what functions are
supported by the air conditioner units.
Note: When setting a schedule for all groups or for a block, it is
possible to set prohibit remote controller items individually.
When allowing remote controller operation under K control,
however, all items must be set enable.
Note: Configurable settings depend on the type of group (Air
Conditioner group, LOSSNAY group, Air-To-Water (PWFY)
group, general equipment group, and HWHP (CAHV) group).
Note: When setting a schedule for ventilator units, the temperature
setting is not displayed. Moreover, the prohibit remote
controller operation is simply [ON/OFF].
Note: Only the ON/OFF operation is possible on the general
equipment.
To copy the schedule of a given day to another day, select the days of
the week from the weekly schedule setting screen, touch [Copy] to
select it, select a day to copy the schedule to, and touch [Paste].
To copy the weekly schedule of one group to another group, select the
group from the weekly schedule setting screen (Floor layout or block
display screen), touch [Copy], select a group to copy the schedule to,
and touch [Paste].
* The settings of one type of equipment cannot be copied to the
settings of a different type of equipment. (i.e., The settings of air
conditioning units cannot be copied to ventilation equipment
(LOSSNAY) settings.)
* Available operation modes and setting temperature range varies
with models.
* Schedules cannot be copied to or from between [Weekly 1] and
[Weekly 5].