ABB i-bus
KNX
Commissioning
Example:
Value pair 1 (VP1)
Control value in % [0...100]
Valve position in % [0...100]
Implemented characteristic curve correction:
Valve position
in %
40
20
Value pair 1
Control value in % [0...100]
Valve position in % [0...100]
Options:
Value pair 2
Control value in % [0...100]
Valve position in % [0...100]
Options:
The possibility of activating other value pairs allows different curve characteristics to be realised.
A total of four value pairs can be set.
38 2CDC 508 101 D0201 | VAA/S x.230.2.1
Control value
Valve position
0...10%
40%
20%
37%
30%
34%
40%
31%
50%
29%
60%
26%
70%
23%
80...100%
20%
VP1
10
0...100
0...100
Value pair 2 (VP2)
Control value in % [0...100]
10
Valve position in % [0...100]
40
VP2
Control value
in %
80
100
80
20