ABB i-bus
KNX
Commissioning
No.
18
This communication object is enabled if in
object "Status control value" is set with the option 1 bit.
The control status of the output is sent via this communication object.
The LED of the corresponding outputs indicates the same value as the status.
The status is sent if
Telegram value:
19
Using the status byte, status information for diagnostic purposes can be read for each output. The current status or
communication object value is sent after a request by the communication object Request status values. The communication
object is always displayed.
The value of the status byte can be decoded using the
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
20-29
30-39
40-49
50-59
60-69
46 2CDC 508 101 D0201 | VAA/S x.230.2.1
Function
Status control value
a request is received via the communication object Request status values and the parameter on request or after a
change or request is present.
the communication object value has changed and the parameter on request or after a change or request is present.
a read request is carried out on this communication object.
0 = control equal to zero; LED
1 = control not equal to zero; LED
Status byte
Control > 0
Telegram value 0: Control = 0
Telegram value 1: Control > 0
Short-circuit
Telegram value: 0 = no short circuit
Telegram value 1: Short circuit
Overload test
Telegram value 0: no overload
Telegram value 1: Overload
Purging
Telegram value 0: Valve purge inactive
Telegram value 1: Valve purge active
Not assigned
Manual operation
Telegram value 0: manual operation inactive
Telegram value 1: manual operation active
Forced operation active
Telegram value 0: forced operation inactive
Telegram value 1: forced operation active
Blocking active
Telegram value 0: Blocking inactive
Telegram value 1: Blocking active
See Output A
Object name
Output A
Parameter window A:
Functions, page 33, the parameter Enable communication
off
on
Output A
Code
table, page 52.
Data type
Flags
1 bit:
C, R, T
DPT 1.011
1 byte
C, R, T
(NON DPT)