Parameter Window Manual Operation - ABB i-bus KNX Product Manual

Valve drive actuator vaa/s x.230.2.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.2.2

Parameter window Manual operation

In this parameter window all the settings for manual operation can be made. For a detailed description of
manual operation see
Manual operation
Options:
This parameter defines if the switch over between the operating states Manual operation and KNX
operation is enabled or disabled via the button
enabled: The operating states Manual operation and KNX operation can be toggled via button
disabled: Manual operation is generally disabled.
disable/enable via communication object: The communication object Disable /enable man. operation
appears.
Telegram value:
If manual operation has been selected with the option enabled or the option disable/enable via
communication object, two further parameters appear:
26 2CDC 508 101 D0201 | VAA/S x.230.2.1
Manual
operation, page 13.
enabled
disabled
disable/enable via communication object
0 = button
1 = button
Reset manual operation to KNX operation
Options:
no
after 1/3/10/30 minutes
This parameter determines how long manual operation remains activated or after how long switch
over to KNX operation occurs.
no: Manual operation remains activated until it is deactivated again using the manual operation
button
or using the communication object.
after X minutes: Manual operation remains activated after the last operation of the button until
the parameterized time has timed out or it is deactivated again using the manual button
on the device or via a communication object.
enabled
disabled
.
.