Comparison of Performance Specifications

The analog product performance specifications are shown in the following tables. Select the optimal product
for your equipment.
4.1

Analog Input

4.1.1
FX
-4AD-ADP
3U
Specifications
Number of input points
Analog input range
Absolute maximum input
Offset
Gain
Digital output
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0 to 55°C
• FX
Time required for A/D
conversion
• FX
Input characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 point (This number is not related to the maximum I/O points of the PLC.)
occupied
PLC User's Manual - Analog Control Edition
Voltage input
0V to 10V DC
(Input resistance: 194 kΩ)
-0.5V, +15V
Impossible to change
12 bits, binary
2.5mV (10V × 1/4000)
±0.5% (±50mV) for 10V full scale
±1.0% (±100mV) for 10V full scale
/FX
Series PLC : 200μs (Data updated every scan time.)
3U
3UC
/FX
/FX
Series PLC : 250μs (Data updated every scan time.)
3S
3G
3GC
4080
4000
0
10V
Analog input
4 Comparison of Performance Specifications
FX
-4AD-ADP
3U
Current input
4ch
4mA to 20mA DC
(Input resistance: 250 Ω)
-2mA, +30mA
Impossible to change
11 bits, binary
10μA (16mA × 1/1600)
±0.5% (±80μA) for 16mA full scale
±1.0% (±160μA) for 16mA full scale
1640
1600
4mA
0
Analog input
4.1 Analog Input
A
B
C
D
E
F
G
H
20mA
I
J
A-27