5.

Changing of Input Characteristics

Use the scaling instruction (SCL/FNC259) for the FX
characteristics. FX
programs to change the input characteristics.
→ For a detailed description of scaling instruction, refer to the FX
5.1

Example: Changing of Voltage Input Characteristics

In the example explained in this section, the voltage input data "1 to 5 V" (Digital output value: 400 to 2000) is
changed to the digital output value "0 to 10000".
1. Input characteristics
C-28
PLC User's Manual - Analog Control Edition
3UC
/FX
/FX
Series PLCs do not support the scaling instruction. Use sequence
3S
3G
3GC
Voltage input characteristics
(product specifications)
4000
2000
400
0
1V
5V
Analog input
5.1 Example: Changing of Voltage Input Characteristics
/FX
Series PLC to change the input
3U
3UC
Programming Manual - Basic & Applied Instruction Edition.
Digital output value to be changed
Y-axis
10000
10V
0
400(1V)
Digital value actually obtained
by A/D conversion
5 Changing of Input Characteristics
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
X-axis
2000(5V)