3U
5.

Changing of Input/output Characteristics

Use the scaling instruction (SCL/FNC259) for the FX
characteristics. FX
programs to change the input/output characteristics.
→ For a detailed description of scaling instruction, refer to the FX
5.1
Example: Changing of Voltage Input Characteristics
This section describes an example of a program that can change the digital output range of 400 to 2000
(when the voltage input is 1 to 5 V) to the digital output range of 0 to 10000.
1. Input characteristics
H-32
PLC User's Manual - Analog Control Edition
3UC
/FX
/FX
Series PLCs do not support the scaling instruction. Use sequence
3S
3G
3GC
Voltage input characteristics
(product specifications)
4000
2000
400
0
1V
5V
Analog input
5 Changing of Input/output Characteristics
5.1 Example: Changing of Voltage Input Characteristics
/FX
Series PLC to change the input/output
3U
3UC
Programming Manual - Basic & Applied Instruction Edition.
Digital output value to be changed
Y-axis
10000
10V
0
400 (1V)
Digital value actually obtained
by A/D conversion
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
X-axis
2000 (5V)