Mitsubishi Electric FX3G User Manual page 365

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-3A-ADP (2-channel Analog Input, 1-channel Analog Output)
3U
• FX
/FX
Series PLC
3U
3UC
The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
into D101. The program will also set "voltage output" for output channels, and set the digital D/A
conversion output to D102.
M8001
Normally OFF
M8000
Normally ON
M8001
Normally
OFF
M8002
Initial
pulse
M8000
Normally
ON
M8000
Normally
ON
M8000
Normally
ON
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly
used in the timer/counter setting value or in a PID instruction.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
PLC User's Manual - Analog Control Edition
M8260
M8261
M8262
M8266
RST
D8268.6
RST
D8268.7
FNC 12
K5
D8264
MOV
FNC 12
K5
D8265
MOV
FNC 12
D8260
D100
MOV
FNC 12
D8261
D101
MOV
FNC 12
D102
D8262
MOV
Set the input mode of channel 1 to the voltage
input mode (0 V to 10 V).
Set the input mode of channel 2 to the current
input mode (4 mA to 20 mA).
Set the output mode to the voltage output mode
(0 V to 10 V).
Set the output holding function.
Error status: b6 = OFF
Error status: b7 = OFF
Set the averaging time to "5" for channel-1 data.
Set the averaging time to "5" for channel-2 data.
Stores the A/D converted channel-1 digital data
into D100.
Stores the A/D converted channel-2 digital data
into D101.
Performs D/A conversion with the digital data
stored in D102.
4 Programming
4.12 Basic Program Example
H-31
A
B
C
D
E
F
G
H
I
J