Bfm#99: Clearance Of Upper/Lower Limit Error Data And Abrupt Change Detection Data; Bfm#101 To #104: Minimum Peak Value / Bfm#111 To #114: Maximum Peak Value - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC

5.4.18 BFM#99: Clearance of upper/lower limit error data and abrupt change detection data

Three error data clearance commands (lower limit error data clearance command, upper limit error data
clearance command, and abrupt change detection data clearance command) are respectively assigned to the
3 lower bits of BFM#99.
Turning on each bit (batch turning on for all channels) will reset the corresponding error status flag (#26 or
#27 of BFM).
1. BFM#99 bits command assignment
Bit No.
b0
b1
b2
b3 to b15
Two or more data clearance commands can be turned on at the same time.
2. Operation after resetting BFM#26, #27
Each bit will turn off automatically.

5.4.19 BFM#101 to #104: Minimum peak value / BFM#111 to #114: Maximum peak value

The minimum channel data (channels 1 to 4) value written to BFM#10 to #13 will be written to BFM#101 to
#104 as the minimum peak value, and the maximum channel data value will be written to BFM#111 to #114
as the maximum peak value.
1. Caution regarding peak value
To use the minimum peak value and the maximum peak value, be sure to turn on the peak value holding
function (b3 of BFM#22).
Note:
• If the data addition function (b0 of BFM#22) is used together with this function, the addition data will be
added to the measurement data.
• If the value holding function is not used, the peak value will be "K0".
• The peak value automatic transfer function is not supported when connected and used with the FX5U or
FX5UC CPU module.
2. Peak value automatic transfer function (b4 of BFM#22)
If the automatic transfer-to first data register is specified in BFM#125, the minimum peak value and the
maximum peak value will be automatically written to the specified data registers (8 points (registers) starting
from the first data register specified).
When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
Convenient function
setting
ON = Valid
BFM#22 b4: ON
BFM#22 b3: ON
PLC User's Manual - Analog Control Edition
Description
Lower limit error data clearance command
Upper limit error data clearance command
Abrupt change detection data clearance command
Not used.
Transfer-from buffer memory
BFM#101 to 104
BFM#111 to 114
Numeric data type: Hexadecimal (H)
Buffer memory to be cleared
Numeric data type: Decimal (K)
 : Represents a numeric value.
Automatic data transfer function
Transfer-to data register specification
(8 points (registers) starting from the
specified data register)
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Initial value: H0000
BFM#26
BFM#27
-
(BFM#125: K
)
D
to D
+3
D
+4 to D
+7
B-41
A
B
C
D
E
F
G
H
I
J