Procedures For Executing Table Output Function - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4DA (4-channel Analog Output)
3U
6.4

Procedures for executing table output function

After setting the output patterns for the channels (BFM#81 to #84) and the number outputs for the channels
(BFM#85 to #88), turn on the table output function start/stop command (BFM#80) to execute the table output
function.
1. Set the output patterns for the channels. (BFM#81 to #84, initial value: K1)
Set the output patterns for the channels in BFM#81 to #84.
The output pattern can be changed in the middle of outputting the table.
Setting range for BFM#81 to #84: 1 to 10
When a value out of the setting range is set, the error code K31 is stored in the table output error code
BFM#90, the number of the buffer memory (K81 to K84) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
2. Set the number of table outputs for the channels. (BFM#85 to #88, initial value: K0)
Set the number of table outputs for the channels in BFM#85 to #88.
The number of outputs can be changed even during outputting the table.
Setting range for BFM#85 to #88: 0 to 32767
When 0 is set, output of the table will be repeated until the table output is stopped by BFM#80.
When a value out of the setting range is set, the error code K32 is stored in the table output error code
BFM#90, the number of the buffer memory (K85 to K88) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
3. Table output start/stop (BFM#80, initial value: H0000)
Table output is started and stopped by setting BFM#80 as shown below.
H
ch4
ch3
Set value
0
1
Other than above values
*1.
When a value out of the setting range is set, the error code K33 is stored in the table output error code
BFM#90, the number of the buffer memory (K80) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
E-48
PLC User's Manual - Analog Control Edition
3UC
ch1
ch2
The table output function of each channel is stopped.
The table output function of each channel is started.
After output of the final point in the last cycle, 0 will be
automatically written.
*1