Setpoint Program Event Alarms - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Function
End Program
Disable Program
Power outage
ATTENTION
hold and the setpoint value will be the setpoint value prior to the beginning of the
setpoint program. The program is placed in hold at the beginning. The mode will be as
configured under "PWR UP" in the "CONTROL" group.
Digital Input (remote switch) operation
Program can be placed in RUN, HOLD, RERUN, or BEGIN state through a remote dry
contact connected to optional digital input terminals, as follows:
RUN—contact closure places Program in RUN state, OR
HOLD—contact closure places Program in HOLD state
RERUN—contact closure allows the Setpoint Programmer to be reset to the initial
segment of its current cycle, unit stays in previous mode.
Opening the contact will cause the Controller to revert to its original state.
BEGIN— Contact closure resets the SP Program back to the beginning of the first
segment in the program and puts the program in the HOLD mode. Program cycle number
is not affected. Reopening the switch has no effect.
Opening the contact will cause the Controller to revert to its original state.

Setpoint Program Event Alarms

See the example in Section 4.21 for help in configuring Alarm Events based upon
segments in the Setpoint Program.
10/05
Press
If power is lost during a program, upon power-up the controller will be in
UDC3500 Universal Digital Controller Product Manual
Monitoring and Operating the Controller
Result
When the final segment is completed, the "R"
in the upper display either changes to "H" (if
configured for HOLD state), or disappears (if
configured for disable of setpoint
programming).
• The controller then either operates at the
last setpoint in the program or goes into
manual mode/failsafe output, depending
upon the "LAST" configuration.
See Section 3 – Configuration Group "SP
PROG" for details.
241