Function Prompt
Lower Display
SW VAL12
SW VAL23
SW VAL34
LSP'S
RSP SRC
10/05
Selections or
Range of Setting
Upper Display
Value in engineering units
within PV or SP range
limits
Value in engineering units
within PV or SP range
limits
Value in engineering units
within PV or SP range
limits
1 ONLY
TWO
THREE
FOUR
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #1 to
Set #2.
ATTENTION Only appears when PID SETS
selection is configured for 2 or 4 PID Sets.
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #2 to
Set #3.
ATTENTION Only appears when PID SETS
selection is configured for 4 PID Sets.
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #3 to
Set #4.
ATTENTION Only appears when PID SETS
selection is configured for 4 PID Sets.
LOCAL SETPOINT SOURCE—This selection
determines what your local setpoint source will be.
LOCAL SETPOINT—The setpoint entered from the
keyboard.
TWO LOCAL SETPOINTS—This selection lets you
switch between two local setpoints using the
SP
SP
SP
Select
Select
Select
key.
THREE LOCAL SETPOINTS—This selection lets
you switch between three local setpoints using the
SP
SP
SP
Select
Select
Select
key.
FOUR LOCAL SETPOINTS—This selection lets you
switch between three local setpoints using the
SP
SP
SP
Select
Select
Select
key.
REMOTE SETPOINT SOURCE—This selection
determines what your remote setpoint source will be
when toggled by the
NONE—No remote setpoint.
INPUT 1—Remote Setpoint using Input 1.
INPUT 2—Remote Setpoint using Input 2.
INPUT 3—Remote Setpoint using Input 3.
Configuration
SP
SP
SP
Select
Select
Select
or Digital Input.