UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
POWER LINE FREQUENCY—Select whether your
controller is operating at 50 or 60 Hertz. Incorrect
setting of this parameter may cause normal mode
noise problems in the input readings.
ATTENTION For controllers powered by +24 Vdc,
this configuration should be set to the AC line
frequency used to produce the +24 Vdc supply.
INPUT 2 RATIO—This enables the Ratio for Input 2
to be set from the front panel. Input 2 must be
installed and enabled for this configuration to
operate.
DISABLE—Disables setting Ratio 2 from front panel.
ENABLE—Allows the Ratio for Input 2 to be set
through the keyboard.
LANGUAGE—This selection designates the prompt
language.
ENGLISH
FRENCH
GERMAN
SPANISH
ITALIAN
IDENTIFICATION NUMBER—This configuration is
used only for uniquely identifying a particular
controller over a communications network. The value
selected has no effect on how the controller
operates.
Configuration