Honeywell UDC3500 Product Manual page 141

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Function Prompt
Lower Display
AUTOBIAS
SP TRACK
PWR MODE
10/05
Selections or
Range of Setting
Upper Display
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN ALG1
IN ALG2
DISABLE
ENABLE
NONE
PV
RSP
MANUAL
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
NONE—No remote setpoint.
INPUT 1—Remote Setpoint using Input 1.
INPUT 2—Remote Setpoint using Input 2.
INPUT 3—Remote Setpoint using Input 3.
INPUT 4—Remote Setpoint using Input 4.
INPUT 5—Remote Setpoint using Input 5.
IN AL1—Remote Setpoint using Input Algorithm 1.
IN AL2—Remote Setpoint using Input Algorithm 2.
ATTENTION To cycle through the available local
setpoints and remote setpoint, press and hold in the
SP
SP
SP
Select
Select
Select
key. When the key is released, the
setpoint selection currently displayed will be the new
setpoint selection.
AUTOBIAS—Used for bumpless transfer when
transferring from any local setpoint to remote
setpoint. This makes the RSP equal to the CSP by
adding, to the input used as the RSP source, a Bias
value. It is changed each time a transfer is made.
Available for any analog input used as the RSP
source.
DISABLE—Disables auto bias.
ENABLE—Enables auto bias.
SETPOINT TRACKING—The local setpoint can be
configured to track either PV or RSP as listed below.
ATTENTION For selections other than NONE,
LSP is stored in nonvolatile memory only when there
is a mode change; i.e., when switching from RSP to
LSP or from Manual to Automatic. If power is lost,
then the current LSP value is also lost.
NO TRACKING—If local setpoint tracking is not
configured, the LSP will not be altered when transfer
from RSP to LSP is made.
PV—Local setpoint tracks the PV when in manual.
RSP—Local setpoint is set equal to the remote
setpoint when a change is made from using remote
setpoint to any local setpoint.
POWER UP CONTROLLER MODE RECALL—This
selection determines which mode and setpoint the
controller will use when the controller restarts after a
power loss.
MANUAL, LSP—At power-up, the controller will use
manual mode with the local setpoint displayed.
Configuration
127