Honeywell UDC3500 Product Manual page 383

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Parameter
Description
ID
Changing the Input Type will result in the loss of Field Calibration values and will restore the
Factory Calibration values.
Input 3
129
Transmitter
Characterization
Input 3 High
27
Range Value
Input 3 Low
28
Range Value
Input 3 Ratio
104
Input 3 Bias
105
Input 3 Filter
33
Input 3 Emissivity
23
10/05
Modbus Read, Write and Override Parameters plus Exception Codes
Register
Address
Hex
Decimal
4081
16513
001B
27
001C
28
0068
104
0069
105
0021
33
4017
16407
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
FP
R/W
–999. to 9999.
Engineering Units
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
0 to 120 seconds
FP
R/W
0.01 to 1.00
Data Range or
369

Advertisement

Table of Contents
loading

Table of Contents