Honeywell UDC3500 Product Manual page 385

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Parameter
Description
ID
Input 4
132
Transmitter
Characterization
Input 4 High
95
Range Value
Input 4 Low
96
Range Value
Input 4 Ratio
97
Input 4 Bias
98
Input 4 Filter
94
Input 4 Burnout
133
10/05
Modbus Read, Write and Override Parameters plus Exception Codes
Register
Address
Hex
Decimal
4084
16516
005F
95
0060
96
0061
97
0062
98
005E
94
4085
16517
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
FP
R/W
–999. to 9999.
Engineering Units
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
–20.00 to 20.00
FP
R/W
–999 to 9999.
Engineering Units
FP
R/W
0 to 120 seconds
INT
R/W
0 = None
1 = Up
2 = Down
3 = No Failsafe
Data Range or