8.6
Monitoring Local Smart Meter Display,
Operation error codes
Table 52
Possible Smart Meter Error Codes.
If error indication is . . .
V A R
SEL.
0
%
0
E r
ANALOG
V A R
SEL.
0
%
1
E r
ANALOG
V A R
SEL.
%
0
E r
2
ANALOG
V A R
SEL.
%
0
3
E r
ANALOG
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Table 52 identifies possible meter error codes and what they mean.
Then, it means
You have tried to set local Zero or Span adjustment in a
Series 100 transmitter which does not support this option.
UPPE R
VALUE
100
UNITS
%
S E T
LOWER
VALUE
You have tried to set a pressure type engineering unit for a
transmitter in SQUARE ROOT mode (FLOW) or have tried
to set a flow type engineering unit for a transmitter in
UPPE R
VALUE
LINEAR mode (pressure). After this error is displayed, the
100
UNITS
meter will return to the unit # (EU#) of the Engineering Unit
%
S E T
it was displaying before the set function was invoked. You
LOWER
may then select another unit or exit in the normal fashion.
VALUE
You have tried to select a process variable for the
transmitter using the VAR SEL. button. The Variable Select
button is non-functioning on the ST 3000 R300 transmitter.
UPPE R
VALUE
100
UNITS
%
S E T
LOWER
VALUE
You have tried to set Lower or Upper display limit for
pressure type engineering units (EU1 to EUC), or Lower
display limit for flow type engineering units (EUD,EUE) or
UPPE R
VALUE
CUSTOM unit (EUF) in transmitter configured for SQUARE
100
ROOT output. Or, you have tried to set upper display limit
UNITS
%
for flow or Custom unit in transmitter with SQUARE ROOT
S E T
output and URV set to zero (0). In SQUARE ROOT mode,
LOWER
VALUE
the transmitter's URV cannot equal zero. The Lower and
Upper display limits only apply for CUSTOM (EUF) unit in
transmitter configured for LINEAR output. The Upper
display limit also applies for FLOW (EUD,EUE) and
CUSTOM (EUF) units with transmitter in SQUARE ROOT
mode , but the Lower display limit is fixed at zero (0) and
cannot be changed.
Continued
Continued on next page
167