Honeywell ST 3000 User Manual page 153

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

7.7
Liquid Level Measurement - Pressurized Tank,
Procedure, continued
Table 42
Starting Up DP Transmitter for Liquid Level Measurement in Pressurized Tank,
continued
Step
Press Key
8
9
10
11
12
F
URV
100%
G
SET
NON-VOL
ENTER
(Yes)
13
INPUT
J
OUT-
PUT
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Read Display or Action
If you ...
Then...
can not fill tank go to Step 9.
can fill tank to
go to Step 10.
desired full-
scale level
Key in URV that is equal to full tank
pressure. See section 6.7 in this manual
for details on keying in a range value.
Close plugs C and D.
Open valves A and B. Fill tank to desired
full scale level.
U R V
1
P T
"
5
Ø
.
Ø Ø Ø
U R V
1
P T
S E T
U
U R V
1
P T
"
5
.
3 2 Ø
Ø
O U T
P
1
P T
S
F C
W O
R K
I N G .
.
O U T
P
1
P T
1 Ø
Ø
.
Ø Ø
Go to Step 14.
Read present URV setting.
3 Ø 1 1
H 2 O _ 3 9 F
Prompt asks if you want to set URV
3 Ø 1 1
to applied pressure.
R V
?
URV is set to full tank pressure.
3 Ø 1 1
H 2 O _ 3 9 F
Call up output for display, with full
3 Ø 1 1
tank pressure applied.
. .
3 Ø 1 1
Read 100% output on display for
%
corresponding full tank pressure.
For analog transmission, check that
milliammeter reading is 20 mA
(100%) output.
Continued
Description
Continued on next page
139

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents