6.12
Configuring Smart Meter Using Pushbuttons,
Setting Upper Display
Values, continued
Table 36
Setting Upper Display Value for Smart Meter Display, continued
Step
3
Press Increase
available magnitude range selection or
Decrease
button to call up previous
magnitude range selection.
NOTE: This action enables the multiplier (K)
for indicating larger ranges and shifts
the decimal point of the digital display
left or right depending on which button
is pushed. The display shows largest
positive number for given range
selection so you can select a range
that is just larger than the range to be
set for best display precision. Hold
respective key to scroll forward or
backward through the selections.
Repeat this action until desired selection is on
display. For example purposes only, largest
range 19990K is selected in this procedure.
4
Press UPPER VALUE button to initiate upper
value setting.
116
ST 3000 Release 300 and SFC Model STS103 User's Manual
Action
button to call up next
Meter Display
Magnitude range selections with largest range
selected.
V AR
SEL.
0
%
19 9 90
ANALOG
K
Press and hold to
scroll backward
19.99
through selections
199.9
1999
19.99K*
199.9K*
1999K*
19990K*
Readout goes blank except for first active digit
which will be 0 unless upper value was set
before.
V A R
SEL.
0
%
00
ANALOG
Continued
UPPE R
VALUE
100
UNITS
S E T
LOWER
VALUE
Press and hold to
scroll forward
through selections
*The "K" multiplier
indicator appears
below the digital
reading on the display.
UPPE R
VALUE
100
UNITS
S E T
LOWER
VALUE
K
Continued on next page
6/05