Enter text to display next to the
breaker graphic during runtime
(optional).
Enter the name of the InTouch analog tag that
determines the color of the circuit breaker
symbol, the state of the breaker, and the status
text displayed next to the breaker icon during
runtime.
21

Circuit Breaker One-Line Wizards

After placing a Horizontal or Vertical Circuit Breaker wizard in a window, double-
click on it to display the dialog box shown below. Configure the wizard by entering
the appropriate information into each of the boxes.
The breaker status values and the associated default colors are listed in the table
below. Error status indicates that the breaker status inputs create an indeterminate
state for the breaker.
Breaker Status
Value
Open
1
Closed
3
Drawn Out
5
Tripped
7
Error
9
Breaker status values & display colors.
Enter the name of the InTouch discrete tag that
determines the color of the line to the right (or
top) of the breaker symbol during runtime.
Text
Default Color
OPN
Green
CLD
Red
OUT
Green
TRP
Yellow
ERR
Flashing Red
Enter the name of
the InTouch discrete
tag that determines
the color of the line
to the left (or bottom)
of the breaker
symbol during
runtime.
Specify the colors of the wizard
elements and status text for the
breaker states during runtime.
See the table below for default
status/color mappings.