EPM 7330 Meter

Tab
Metering
MIN/MAX Demand
126
The EPM 7330 Tabular Data Screen wizard has several special features. You can use
the Setup screen to change the meter configuration. Values displayed in white boxes
are changeable. Some are changed by clicking on the displayed value, while others
are changed by clicking on the associated scroll button. The Download and Refresh
buttons on the setup screen upload and download all of the setpoints from the device.
To change setpoints at the device, first press the refresh button to upload current
setpoint values from the device (otherwise the defaults are shown and used for
download). Modify setpoints as desired, then press the download button to send all
setpoints to the unit.
The EPM 7330 Tabular Data Screen's command buttons are described below:
Button
Function
Reset Energy
Resets all Energy Integrators in the meter.
Digital Input Labels
The user can enter descriptive text (up to 20 characters) for each digital
input. These labels are retentive.
Force ON
For each digital output, this button will force the output to the ON state.
Force OFF
For each digital output, this button will force the output to the OFF state.
Reset Sliding
Resets all Sliding Demand Values in the device.
Demand
Reset Min/Max
Resets all Min/Max values in the device.
Table 22. EPM 7330 Tabular data screen commands