Calibration

Position Sensor Calibration

Step
1
Prepare for calibration by performing the steps shown in your actuator manual's calibration
section, then return here.
2
From the Home page, select the "Calibration" prompt.
3
Select the "NCS" prompt from the list of calibration functions.
The functionality of each button is described below.
Setup – Has no functionality in the NCS calibration procedure.
Function – Sequences you through the calibration states.
Auto/Man – Has no functionality in the NCS calibration procedure.
Display – Has no functionality in the NCS calibration procedure.
Increment – Has no functionality in the NCS calibration procedure.
Decrement – Has no functionality in the NCS calibration procedure.
Close – Exits from the NCS calibration.
Note: If calibration is locked out, then accessing the NCS calibration will display an
error message "The device sent an invalid response".