Step
5
Select the "Input" prompt. The functionality of each button is described below:
Setup – Has no functionality in the input calibration procedure.
Function – Sequences you through the calibration states.
Auto /Man – Has no functionality in the input calibration procedure.
Display – Has no functionality in the input calibration procedure.
Increment – Has no functionality in the input calibration procedure.
Decrement – Has no functionality in the input calibration procedure.
Close – Exits from the input calibration.
Note: If calibration is locked out, then accessing the input calibration will display an
error message "The device sent an invalid response".
Release 1
8/06
Action
HercuLink™ User Manual
Calibration
15