Calibration
Step
6
Click the "Function" button to access the "Apply Zero Count" Calibration state.
The output voltage can be adjusted up or down by clicking the Incr + 10%, Decr – 10%,
Increment and Decrement buttons. Click any button as many times as necessary to get to the
output voltage level desired. Typically 1.00vdc for 4–20mA and 0.0vdc for 0–20mA.
Note: If at any time an error message is displayed, this is an indication that
communications between the PC and the unit have been lost. To check
communications, see Preparation on page 1.
30
Action
HercuLink™ PC - User Manual
Release 1
8/06