MA-LCD7 Programming

MA-LCD7 can be programmed to function as a Repeater or as a Zonal Mimic. As default, the MA-LCD7 will be
supplied pre-programmed to operate as an active Repeater (MA-LCD7). Option to program as virtual zonal
Mimic (MA-LCD7M) must be done during the Firmware upgrade process. Upgrading or re-flashing the firmware
provides the option to select the MA-LCD7 function.
The Repeater/Mimic firmware is available to download from the following URL:
https://buildings.honeywell.com/gb/en/lp/morleymaxtech
A USB flash drive with a memory size greater the 500 MB is required as part of the firmware
upgrade process. A single MA-LCD7 firmware file (.UPD) contains both Repeater (MA-LCD7) and
Zonal Mimic (MA-LCD7M) functionality. Each function is selected on the MA-LCD7 upon start
up. After selection the MA-LCD7 will reboot in the selected functionality.

5.1 Steps for Programming Repeater/Mimic function

1.
Download the latest MA-LCD7 Firmware file (.UPD) and add the file to your USB drive.
2.
Ensure MA-LCD7 is powered up (if not already).
3.
Select [UTIL] Menu button.
4.
Select the 'Update Firmware' option.
5.
Insert the USB flash drive into the USB port, located at the bottom of the MA-LCD7.
6.
Confirmation box will appear. Select 'OK'.
7.
MA-LCD7 will now power down and reboot displaying the function selection screen.
8.
Select the MA-LCD7 function:
a. MA-LCD7 = Functional Repeater
b. MA-LCD7M = Zonal Mimic
9.
After selecting the function, the MA-LCD7 will reboot again and start up in the selected function.
10. Remove the USB flash drive.
M-167.6-MA-LCD-EN / 10.2023