Honeywell GENT VIG-RPT-72 Installation Manual

Honeywell GENT VIG-RPT-72 Installation Manual

Vigilon repeat panel (en/bs)

Advertisement

www.acornfiresecurity.com
Data and installation
Vigilon Repeat panel (EN/BS)
VIG-RPT-72
Panel healthy
Vigilon Fire System
GENT 2010
The repeat panel duplicates all of the control panel
indications and the essential controls.
The repeat panel has its own mains derived power
supply with battery for standby power in the event
of mains supply failure. A lockable front door
prevents unauthorised access to fire alarm controls
but allows all of the indicators to be seen. The
panel is designed for semi-flush or surface
mounting and facilitates both rear and top cable
entry points.
This repeat panel can be installed on a loop circuit
of an EN or BS Vigilon fire detection and alarm
system. It can be sited near an entry or exit point
of a building and fit in with the loop cable routing.
Compatibility
The repeat panel is compatible with system control
panel having card and software below:
Control panel
Control Panel Software
CARD
EN54
³ V4.00
LCC
³ V4.19
LPC
New Shorter
Card ONLY
³ V4.11
MCC
³ V4.21
MCB
³ means equal to or greater than
4188-839_issue 8_07/14_pt1_EN/BS new Repeat_inst
www.acornfiresecurity.com
Technical Data
Panel dimensions
Weight
15:45
Storage temperature -10°C to +55ºC
Operating
temperature
Relative humidity
(Non condensing)
Battery
Mains operating
voltage
Rated Current
Emission
Immunity
LVD
Ingress protection
Colour
Controls
(with door closed)
Access level 1
Control buttons
(with door open)
Access level 2
Indicators
BS5839
³ 3.42
Loop connection
³ 3.90
EN54-17 data
Fire detection and
fire alarm system
-
short circuit isolators
-
by Honeywell
height 403mm, width 338mm,
depth 101mm
9Kg with battery (approximate)
0°C to +45ºC
Up to 90% temperature
+5°C to +45°C
12V 7Ah sealed lead acid
230V -15% +10% 50/60Hz
0.2A
BS EN61000-6-3 : 2001
BS EN50130-4 : 1996 : Part 4
BS EN 60950-2006
IP31 (estimated)
Door - Pantone 422
Back box - Graphite Grey (RAL 7024)
Next and Previous buttons operable
during fire condition only.
Sound Alarms, Silence Alarms, Reset
Fire, Cancel Fault Buzzer, Verify,
F1-F4, Menu On/Off and U1-U4.
Fire, Verify, Power, Fault, Power Fault,
System Fault, Delay and CB253/254.
EN panel only: Sounder, Sounder,
Delay, Disablement Test and 32-Fire
Zone LEDs.
BS panel only: Commission and
Warning.
Display: 8 lines 40 characters per line,
back-lit LCD.
3-way connection to a loop circuit
V
42V
V
max
nom
V
24V
V
min
SO max
I
V
8V
SO min
C max
I
I
1A
S max
L max
Z
0.1W
C max
40V
16V
0.4A
20mA
1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell GENT VIG-RPT-72

  • Page 1 Data and installation Vigilon Repeat panel (EN/BS) by Honeywell VIG-RPT-72 Technical Data Panel dimensions height 403mm, width 338mm, depth 101mm Weight 9Kg with battery (approximate) Panel healthy 15:45 Vigilon Fire System GENT 2010 Storage temperature -10°C to +55ºC Operating 0°C to +45ºC...
  • Page 2: Installation

    www.acornfiresecurity.com Data and installation Vigilon Repeat panel (EN/BS) Refit the temporary cover to protect the panel Installation until all building work is complete. Cross section of the wall to which The Repeat Panel Set consists of: the panel is to be semi-flush mounted Parts Aperture depth should Aperture...
  • Page 3: Membrane Labels For Bs Repeat Panel

    www.acornfiresecurity.com Vigilon Repeat panel (EN/BS) Data and installation From Mains fused spur Loop IN Loop OUT Loop COM Spur Connection Loop IN Loop OUT Repeat panel mains Zones Fault Fire inner and outer Panel healthy 15:45 Power Fault Verify fy System Fault XXXXX --- Fire Alarm System GENT 2007...
  • Page 4: Zone Indicators

    www.acornfiresecurity.com Zone indicators Contrast and Emergency controls The zone indicators are not used on a BS Repeat panel. The LCD Contrast adjust links that disable the zone indicators are located on the bottom Anti-Clockwise - Lighter edge of the DKC and must be set to 'Without zone indicators' position.
  • Page 5 Commissioning information Vigilon Repeat panel (EN/BS) by Honeywell VIG-RPT-72 The following checks and tests should be Buzzer Disable Link conducted on each installed Repeat panel to During system commissioning it may be necessary to fit a link (not suppllied) ensure the basic functions are operating correctly.
  • Page 6: Commissioning Information

    www.acornfiresecurity.com Commissioning information Vigilon Repeat panel (EN/BS) How to create an Engineer PIN Password or PIN code " " All Vigilon panels leave the factory with no Engineer PIN code The terms Password, PIN (Personal (Access level 3 code). Therefore, on first power up there is an Identification Number), Usercode and Access code open access to all the Access level 3 menus.
  • Page 7 www.acornfiresecurity.com Vigilon Repeat panel (EN/BS) Commissioning information " Menu maps The full repeat panel menu maps will only be accessible following the allocation of the loop on which the panel resides. 4188-839_issue 7_08/12_pt2_EN/BS Repeat_inst www.acornfiresecurity.com...
  • Page 8 www.acornfiresecurity.com Commissioning information Vigilon Repeat panel (EN/BS) 4188-839_issue 7_08/12_pt2_EN/BS Repeat_inst www.acornfiresecurity.com...
  • Page 9 www.acornfiresecurity.com Vigilon Repeat panel (EN/BS) Commissioning information 4188-839_issue 7_08/12_pt2_EN/BS Repeat_inst www.acornfiresecurity.com...

Table of Contents