Honeywell MA-LCD Operating And Installation Manual page 37

Repeater / zonal mimic
Table of Contents

Advertisement

Selecting the Zone - using the select key
Selected Zone Number. 'Zone n. 1' = Zone 1
Using the arrow keys
First Fault details: Example:
'F:C1L1S1 (MULTI) 14:36:21 25-04-2023 (1)'
'Label for Panel 1 – Label for Multi-Dect'
'Invalid reply to Detector'
= Location on device/address – [F:C1L1S1] = Alarm C1=CPU/Panel number 1, L1= Loop Number 1, S1
= Detector address 1. [(MULTI)] device type ID = Multi (Multi criteria detector (opt/heat, opt/heat/IR)),
[14:36:21 25-04-2023] = Time and Date of activation, (1) = Event number within the selected Zone.
[Label for panel 1] = CPU/Panel label, [Label for Multi-Dect] = Device Label
[Invalid reply to Detector] = Fault reported on device
M-167.6-MA-LCD-EN / 10.2023
, users can view the details of the device(s) in Fault.
user can highlight the devices in Fault. Arrow keys will also scroll
MA-LCD Repeater / Zonal Mimic