MA-LCD Repeater / Zonal Mimic
6

MA-LCD7 Addressing

Each MA-LCD7 must be programmed with a unique address between 1-16. Addresses can be repeated
throughout a Networked system, but not on the same serial line.
As default, all Repeaters/Mimics will be addressed as '0', Users are required to change the address between
1-16 upon start up. If more than one MA-LCD7 is required on the same serial line, then the address of the new
MA-LCD7 Repeater must be programmed.
To program the MA-LCD7 address. This option is located in the Utility Menu (access Level 2 required).
Utility> Address

6.1 MA-LCD7M Mimic Addressing

MA-LCD7 programmed as a Mimic (MA-LCD7M). The address of the mimic also programs the zonal range to be
displayed. 1 – 1120. Please see table below.
MA-LCD7M Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
The following addresses are reserved for the MA-LCD7-MOD (MA-8000 only) Starting range from 41.
15
16
16
Mimic Zonal Range
1 - 80
81 - 160
161 - 240
241 - 320
321 – 400
401 - 480
481 - 560
561 - 640
641 – 720
721 - 800
801 - 880
881 - 960
961 - 1040
1041 - 1120
41 - 120
121 - 200
Use the arrow keys to select the option for
Address.
Select the address number by pressing the enter
key
.
Use the arrow keys to select the MA-LCD7
address between 1 – 16.
To confirm the selected address, press the enter
key
.
M-167.6-MA-LCD-EN / 10.2023