Honeywell FIre-LITe ALArms MS-9600LS Manual page 81

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Master Programming Level
If the selected address corresponds to a monitor module, a screen displaying information about the
module with the selected address will be displayed as illustrated in the following:
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No is selected, the module will not be polled by the control panel, preventing the module from
reporting alarms and troubles to the panel. The control panel will indicate a system trouble condi-
tion and the Disable LED with turn on if any devices are disabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
NORMAL MONITOR
<ADJ><NOUN>
EDIT MONITOR
1=ENABLED
2=TYPE
MONITOR
Edit Monitor Screen #2
EDIT MONITOR
1=PRE-SIGNAL
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Monitor Screen #5
ZNNN
1M012
1M012
YES
1M012
NO
1M012
YES
1M012
Programming
81