Accessories
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
Specifications
•
Max. ANN-BUS Voltage: 24 VDC
•
Max. Current:
• Alarm: 68 mA
• Standby: 28 mA
•
Operating Temperature: 32
•
For indoor use in a dry location only
Mounting/Installation
Refer to the documentation supplied with the ANN-LED module for mounting information.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Figure 1.11 ANN-LEDs (shown in possible stacked configuration)
o
F to 120
Figure 1.12 Exploded View of ANN-LED
o
o
o
F (0
C to 49
C)
Product Description
35