Honeywell FIre-LITe ALArms MS-9600LS Manual page 25

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Accessories
The total worst case current is calculated as follows:
ANN-80 Current Draw
ANN-S/PG Current Draw
ANN-I/O Current Draw
Total Worst Case Current Draw
Using this value and referring to the Wiring Distance Table 1.1 on page 24, it can be found that the
available options are:
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
= 3 X 0.040 amps
= 1 X.0.040 amps
= 1 X.0.200 amps
ANN-BUS and power wiring are
supervised and power-limited
B A (+) (-)
TB1
4 3 2 1
ANN-BUS Device
+ - + - + -
TB3
Figure 1.3 FACP wiring to ANN-BUS Device
= 0.120 amps
= 0.040 amps
= 0.200 amps
= 0.360 amp
24 VDC
nonresettable
TB1
TB5
TB4
JP8
FACP
Product Description