Master Programming Level
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
The following examples show the editing of a photoelectric smoke detector with address 017,
located on the first SLC loop:
EDIT DETECTOR 1D017
1=ENABLED
2=TYPE
3=VERIFICATION
EDIT DETECTOR 1D017
1=WALKTEST
2=PAS
3=PRE-SIGNAL
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
EDIT DETECTOR 1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the detector will not be polled by the control panel, preventing the detector from reporting
alarms and troubles to the panel. The control panel will display the device type and address which
has been disabled and will turn on the Trouble LED and Disable LED.
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
Screen #2. This will cause the control panel to display the following Detector Type Screens:
1=SMOKE PHOTO
2=USER DEFINED-1
3=SMOKE (ION)
SMOKE(PHOTO)
Edit Detector Screen #2
Edit Detector Screen #3
00 ** ** ** **
Edit Detector Screen #4
Edit Detector Screen #5
DETECTOR TYPE
Detector Type Screen #1
Programming
YES
OFF
NO
NO
NO
71