Master Programming Level
ANNUNCIATORS
Pressing 2 for ACS Options while viewing the Annunciators screen, will display the following
1=TERM OPTIONS
screen:
2=ACS OPTIONS
3=ANN-BUS OPTIONS
Annunciator Screen
Pressing 1 while viewing the ACS Options screen will cause the display to toggle between ACS
Enabled Yes and ACS Enabled No. To install an ACS annunciator, the display must read ACS
Enabled Yes.
If ACS has been enabled, press 2 while viewing the ACS Options screen to select addresses for the
ACS annunciators. The following screen will be displayed:
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 -31. Each screen will indicate if an address has been used for an installed ACS annun-
ciator. To select one or more addresses for the installed ACS annunciator(s), press the number key
corresponding to the address in each screen. The display for the selected address will change from
No to Yes. Each press of the number key will cause the display to toggle between No and Yes. The
address of each installed annunciator must be enabled to allow communication between the FACP
and annunciator.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
ACS Options
1=ACS ENABLED
2=ACS INSTALLED
3=UDACT
1=ADDRESS 1
2=ADDRESS 2
3=ADDRESS 3
ACS OPTIONS
ANNUNCIATOR
ACS Installed Screen
Programming
NO
NO
YES
NO
NO
119